Evaluation of low cost radiant cooling panel in a test room with passively cooled water
Muhammad Syukri Imran,
Azhaili Baharun,
Siti HalipahIbrahim and
Wan Azlan Wan Zainal Abidin
Additional contact information
Muhammad Syukri Imran: Universiti Malaysia Sarawak, Kota Samarahan, Malaysia
Azhaili Baharun: Universiti Malaysia Sarawak, Kota Samarahan, Malaysia
Siti HalipahIbrahim: Universiti Malaysia Sarawak, Kota Samarahan, Malaysia
Wan Azlan Wan Zainal Abidin: Universiti Malaysia Sarawak, Kota Samarahan, Malaysia
Journal of Advances in Technology and Engineering Research, 2017, vol. 3, issue 5, 211-223
Abstract:
Public acceptance in low energy hydronic radiant cooling system is almost none in country like Malaysia. This is due to the low awareness of the performance and benefit of such system in the country as well as higher initial construction cost. With the aim of long term energy and cost saving this study looks into the performance of custom built radiant cooling surface panel that was retrofitted in a test room located in Kuching Sarawak. In climate condition like Malaysia where only cooling is required, the radiant panel needs only to be a cooling surface unlike its overseas counterpart that heats or cools interchangeably according to the changing seasons. This allows the use of alternative low cost material such as PVC to replace the more common radiant tubing like copper or cross-linked Polyethylene (PEX) tube. A test room was retrofitted with PVC tubing radiant ceiling panel and connected to a chill water tank. The water was passively cooled during the night using the pitch roof as a heat exchanger to chill the water to as low as 24°C. The water was then used to charge the hydronic ceiling radiant panel during the day time when the outdoor temperature exceeds 30°C. The experiment shows that the system was able to maintain an indoor temperature to about 30°C when the outdoor temperature peaked to 34°C while providing acceptable thermal comfort. The experiment showed that the use of the hydronic radiant panel with free night cooled water as its coolant have significant energy saving potential while at the same time provide an acceptable room thermal comfort. The locally built radiant panel and easy to install night cooling rig could be an attractive choice as a Malaysian building cooling system that complies to a bioclimatic building principle.
Keywords: Radiant Cooling Panel; Energy Savings; Thermal Comfort; Cooling Capacity; PVC Tube (search for similar items in EconPapers)
Date: 2017
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
https://tafpublications.com/platform/Articles/full-jater3.5.5.php (application/pdf)
https://tafpublications.com/gip_content/paper/Jater-3.5.5.pdf (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:apb:jaterr:2017:p:211-223
DOI: 10.20474/jater-3.5.5
Access Statistics for this article
Journal of Advances in Technology and Engineering Research is currently edited by A/Professor Akbar A. Khatibi
More articles in Journal of Advances in Technology and Engineering Research from A/Professor Akbar A. Khatibi Calle Alarcon 66, Sant Adrian De Besos 08930, Barcelona Spain.
Bibliographic data for series maintained by A/Professor Akbar A. Khatibi ().