EconPapers    
Economics at your fingertips  
 

Investigation on the Regeneration and Corrosion Characteristics of an Anodized Aluminum Plate Regenerator

Tao Wen, Lin Lu, Hongxing Yang and Yimo Luo
Additional contact information
Tao Wen: Renewable Energy Research Group, Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China
Lin Lu: Renewable Energy Research Group, Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China
Hongxing Yang: Renewable Energy Research Group, Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China
Yimo Luo: Faculty of Science and Technology, Technological and Higher Education Institute of Hong Kong, Hong Kong, China

Energies, 2018, vol. 11, issue 5, 1-15

Abstract: The traditional vapor compression cooling system (VCS) has been criticized for its heavy reliance on electricity consumption and limited control ability of humidity. Compared with the VCS, the liquid desiccant cooling system (LDCS) is more efficient by handling the sensible and latent load separately. The present study investigated the regeneration and corrosion characteristics of an anodized aluminum plate regenerator for the first time. Comparative tests were conducted to present the regeneration and corrosion characteristics of the normal and anodized regenerator. The influence of internal heating on the regeneration performance was also identified. The results showed that the corrosion rate was reduced from 0.0005218 mm/year for normal aluminum to 0.000011 m/year for anodized one under the same operating conditions. However, pitting corrosion was observed at operating conditions with high solution temperature, as the anodized layer of anodized aluminum was damaged due to the high temperature. Compared with the normal aluminum regenerator, the anodized one had an average enhancement of 24% and 23.7% in terms of regeneration rate and effectiveness, respectively. It was attributed to the increment of surface energy from 26.4 mN/m for normal aluminum to 47.6 mN/m for anodized plate. Besides, it was found that, compared with adiabatic one, the internally-heated regenerator improved the regeneration rate by 6.0%~38% and the regeneration effectiveness by 6.3%~32% depending on the operating conditions. The advantage of present study is that it can guide the design of anodized aluminum regenerator for LDCS.

Keywords: falling film regeneration; internal heating; corrosion; surface energy; anodized aluminum plate (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2018
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (3)

Downloads: (external link)
https://www.mdpi.com/1996-1073/11/5/1209/pdf (application/pdf)
https://www.mdpi.com/1996-1073/11/5/1209/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:11:y:2018:i:5:p:1209-:d:145443

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:11:y:2018:i:5:p:1209-:d:145443