Finite Control Set Model Predictive Control for an LCL-Filtered Grid-Tied Inverter with Full Status Estimations under Unbalanced Grid Voltage

Xiaotao Chen, Weimin Wu, Ning Gao, Jiahao Liu, Henry Shu-Hung Chung and Frede Blaabjerg
Additional contact information
Xiaotao Chen: Department of Electronic Engineering, Shanghai Maritime University, Shanghai 201306, China
Weimin Wu: Department of Electronic Engineering, Shanghai Maritime University, Shanghai 201306, China
Ning Gao: Department of Electronic Engineering, Shanghai Maritime University, Shanghai 201306, China
Jiahao Liu: Department of Electronic Engineering, Shanghai Maritime University, Shanghai 201306, China
Henry Shu-Hung Chung: Department of Electronic Engineering, City University of Hong Kong, Hong Kong 999077, China
Frede Blaabjerg: Department of Energy Technology, Aalborg University, DK-9220 Aalborg, Denmark

Energies, 2019, vol. 12, issue 14, 1-22

Abstract: This paper proposes a novel finite control set model predictive control (FCS-MPC) strategy with merely grid-injected current sensors for an inductance-capacitance-inductance (LCL)-filtered grid-tied inverter, which can obtain a sinusoidal grid-injected current whether three-phase grid voltages are balanced or not. Compared with the conventional FCS-MPC method, four compositions are added in the proposed FCS-MPC algorithm, where the grid voltage observer (GVO) and Luenberger observer are combined together to achieve full status estimations (including grid voltage, capacitor voltage, inverter-side current, and grid-injected current), while the sequence extractor and the reference generator are applied to eliminate the double frequency ripples of the active or reactive power, or the negative sequence component (NSC) of the grid-injected current caused by the unbalanced grid voltage. Simulation model and experimental platform are established to verify the effectiveness of the proposed FCS-MPC strategy, with full status estimations under both balanced and unbalanced grid voltage conditions.

Keywords: finite control set model predictive control (FCS-MPC); full status estimations; grid voltage observer (GVO); inductance-capacitance-inductance (LCL)-filtered grid-tied inverter; Luenberger observer (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2019
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (9)

Downloads: (external link)
https://www.mdpi.com/1996-1073/12/14/2691/pdf (application/pdf)
https://www.mdpi.com/1996-1073/12/14/2691/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:12:y:2019:i:14:p:2691-:d:248128

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:12:y:2019:i:14:p:2691-:d:248128