Development of Virtual Air Flow Sensor Using In-Situ Damper Performance Curve in VAV Terminal Unit
Hyo-Jun Kim,
Jae-Hun Jo and
Young-Hum Cho
Additional contact information
Hyo-Jun Kim: Department of Architectural Engineering, Graduate School of Yeungnam University, 280 Daehak-Ro, Gyeongsan 38541, Korea
Jae-Hun Jo: Division of Architecture, Inha University, 100 Inha-ro, Incheon 22212, Korea
Young-Hum Cho: School of Architecture, Yeungnam University, 280 Daehak-Ro, Gyeongsan 38541, Korea
Energies, 2019, vol. 12, issue 22, 1-14
Abstract:
In this study, we developed a virtual air flow sensor using an in-situ damper performance curve to secure the stability of control of the variable air volume (VAV) terminal unit, and also established the in-situ measurement procedure. The minimum air flow rate of the VAV terminal unit was related to the energy consumption, it was important to determine the minimum air flow rate suitable for the situation of each room in terms of energy saving. However, it was difficult to set the minimum air flow rate low setpoint due to the low accuracy of the air flow sensor of the VAV terminal unit. This paper suggested a virtual air flow sensing method using an in-situ damper performance curve in the VAV terminal unit. The input factors of the virtual sensor were developed on the basis of the supply fan speed and damper opening ratio, which could be easily obtained from the existing control system. In addition, the in-situ measurement procedure of the virtual air flow sensor was developed by dividing the procedure into five steps. Finally, reliability of the virtual air flow sensor was evaluated through uncertainty analysis of input variables and relative error analysis, in comparison with the conventional air flow rate measurement method. The developed virtual air flow sensor was found to have an uncertainty of up to 8.8%, and it was also found that the closer to the maximum the values of the input variables, the lower the uncertainty. In addition, verification of relative error with respect to the measured values by the hot-wire anemometer was conducted by varying operation conditions to a total of 12 cases, and as a result, relative error was found to be up to 5.6%. In addition, the results of long-term experiment showed that relative error was within about 9.5%, and thus, the feasibility for field application and control was confirmed.
Keywords: variable air volume system; terminal unit; in-situ damper performance curve; air flow rate; virtual sensor (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2019
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
https://www.mdpi.com/1996-1073/12/22/4307/pdf (application/pdf)
https://www.mdpi.com/1996-1073/12/22/4307/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:12:y:2019:i:22:p:4307-:d:286098
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().