Analysis of the Electrical Quantities Measured by Revenue Meters Under Different Voltage Distortions and the Influences on the Electrical Energy Billing
Roberto Perillo Barbosa da Silva,
Rodolfo Quadros,
Hamid Reza Shaker and
Luiz Carlos Pereira da Silva
Additional contact information
Roberto Perillo Barbosa da Silva: Department of Systems and Energy, University of Campinas, Campinas 13083-852, Brazil
Rodolfo Quadros: Department of Systems and Energy, University of Campinas, Campinas 13083-852, Brazil
Hamid Reza Shaker: Center for Energy Informatics, University of Southern Denmark, 5230 Odense, Denmark
Luiz Carlos Pereira da Silva: Department of Systems and Energy, University of Campinas, Campinas 13083-852, Brazil
Energies, 2019, vol. 12, issue 24, 1-18
Abstract:
This paper evaluates the impact of voltage distortion on the electrical quantities measured by revenue meters and the influences on the electrical energy billing. This is done through an experimental setup, which combines the following variables for the first time in an experiment: different total harmonic voltage distortion (THDv) levels; among these levels, different harmonic profiles; and different loads. A programmable alternating current (AC) power source was used in the laboratory to apply voltage signals in three electronic loads: a compact fluorescent lamp (CFL) and two light emitting diode (LED) lighting devices for which voltage signals with THDv 4.9%, 18.8% and 24.5% have been applied. All applied signals contain one or more harmonic order more commonly found in the low voltage grid (3rd, 5th and 7th). For these analyses, a power quality analyzer and a revenue meter were used. The results show that significant and diverse effects on the electrical quantities of individual loads will occur with different THDv levels and harmonic profiles. Comparing with a reference case (sinusoidal condition), when a distorted signal was applied, for the same THDv level, some parameters remained numerically the same, some have improved and some have become worse. This study shows that the effects of combination of the variables such as different THDv level with different harmonic profiles on electrical quantities of loads are not as clear as the effects of considering only one variable. The results of this paper shed light on such effects.
Keywords: harmonic distortion; measurement; nonlinear loads; power factor; power quality (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2019
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (3)
Downloads: (external link)
https://www.mdpi.com/1996-1073/12/24/4757/pdf (application/pdf)
https://www.mdpi.com/1996-1073/12/24/4757/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:12:y:2019:i:24:p:4757-:d:297604
Access Statistics for this article