Energies, 2020, vol. 13, issue 20, 1-15
Abstract:
An experimental study regarding the thermofluid characteristics of a shell-and-plate heat exchanger with different chevron angles (45°/45°, 45°/65°, and 65°/65°) with a plate diameter of 440 mm was carried out. Water was used as the working fluid on both sides and the corresponding temperatures ranged from 30–70 °C. The flow rate on the plate or shell side ranged from 10–60 m 3 /h. The effects of chevron angles on the heat transfer and fluid flow characteristics of shell-and-plate heat exchangers were studied in detail. With regard to the heat transfer performance on the plate side, a higher chevron angle (65°/65°) resulted in a significantly better performance than a low chevron angle (45°/45°). The effect of the chevron angle became even more pronounced at high Reynolds numbers. Unlike the plate side, an increase in the chevron angle had a negative effect on the heat transfer performance of the shell side. Additionally, this opposite effect was more prominent at low Reynolds numbers due to the comparatively large contribution of the manifold. The friction factor increased appreciably with the increase in the chevron angle. However, when changing the chevron angle from 45°/45° to 65°/65°, the increase in the friction factor was about 3–4 times on the plate side while it was about 2 times on the shell side. This can be attributed to the presence of the distribution/collection manifold on the shell side. Empirical correlations for the Nusselt number and friction factor were developed for different combinations of chevron angles with mean deviations of less than 1%.
Keywords: shell-and-plate heat exchanger; chevron angle; heat transfer; Nusselt number; friction factor; correlations (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2020
References: View complete reference list from CitEc
Citations: View citations in EconPapers (2)
Downloads: (external link)
https://www.mdpi.com/1996-1073/13/20/5304/pdf (application/pdf)
https://www.mdpi.com/1996-1073/13/20/5304/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:13:y:2020:i:20:p:5304-:d:426745
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().