Effects of Positioning of Multi-Sensor Devices on Occupancy and Indoor Environmental Monitoring in Single-Occupant Offices
Shoaib Azizi,
Ramtin Rabiee,
Gireesh Nair and
Thomas Olofsson
Additional contact information
Shoaib Azizi: Department of Applied Physics and Electronics, Umeå University, 901 87 Umeå, Sweden
Ramtin Rabiee: Department of Applied Physics and Electronics, Umeå University, 901 87 Umeå, Sweden
Gireesh Nair: Department of Applied Physics and Electronics, Umeå University, 901 87 Umeå, Sweden
Thomas Olofsson: Department of Applied Physics and Electronics, Umeå University, 901 87 Umeå, Sweden
Energies, 2021, vol. 14, issue 19, 1-23
Abstract:
The advancements in sensor and communication technologies drive the rapid developments in the applications of occupancy and indoor environmental monitoring in buildings. Currently, the installation standards for sensors are scarce and the recommendations for sensor positionings are very general. However, inadequate sensor positioning might diminish the reliability of sensor data, which could have serious impacts on the intended applications such as the performance of demand-controlled HVAC systems and their energy use. Thus, there is a need to understand how sensor positioning may affect the sensor data, specifically when using multi-sensor devices in which several sensors are being bundled together. This study is based on the data collected from 18 multi-sensor devices installed in three single-occupant offices (six sensors in each office). Each multi-sensor device included sensors to measure passive infrared (PIR) radiation, temperature, CO 2 , humidity, and illuminance. The results show that the positions of PIR and CO 2 sensors significantly affect the reliability of occupancy detection. The typical approach of positioning the sensors on the ceiling, in the middle of offices, may lead to relatively unreliable data. In this case, the PIR sensor in that position has only 60% accuracy of presence detection. Installing the sensors under office desks could increase the accuracy of presence detection to 84%. These two sensor positions are highlighted in sensor fusion analysis as they could reach the highest accuracy compared to other pairs of PIR sensors. Moreover, sensor positioning can affect various indoor environmental parameters, especially temperature and illuminance measurements.
Keywords: data reliability; sensor placement; IoT; sensor accuracy; PIR sensors; sensor fusion (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2021
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (2)
Downloads: (external link)
https://www.mdpi.com/1996-1073/14/19/6296/pdf (application/pdf)
https://www.mdpi.com/1996-1073/14/19/6296/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:14:y:2021:i:19:p:6296-:d:648915
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().