Impact of Weather Conditions on the Operation of Power Unit Cooling Towers 905 MWe
Zbigniew Buryn,
Anna Kuczuk,
Janusz Pospolita,
Rafał Smejda and
Katarzyna Widera
Additional contact information
Zbigniew Buryn: Faculty of Production Engineering and Logistics, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland
Anna Kuczuk: Faculty of Mechanical Engineering, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland
Janusz Pospolita: Faculty of Mechanical Engineering, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland
Rafał Smejda: PGE GIK S.A. Branch Opole Power Plant, Brzezie k., 46-021 Opola, Poland
Katarzyna Widera: Faculty of Economics and Management, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland
Energies, 2021, vol. 14, issue 19, 1-19
Abstract:
The paper presents the results of measurements and calculations concerning the influence of weather conditions on the operation of wet cooling towers of 905 MWe units of the Opole Power Plant (Poland). The research concerned the influence of temperature and relative humidity of air, wind and power unit load on the water temperature at the outlet from the cooling tower, the level of water cooling, cooling efficiency and cooling water losses. In the cooling water loss, the evaporation loss stream and the drift loss stream were distinguished. In the analyzed operating conditions of the power unit, for example, an increase in T a m b air by 5 °C (from 20 – 22 ° C to 25 – 27 ° C ) causes an increase in temperature at the outlet of the cooling tower by 3 – 4 ° C . The influence of air temperature and humidity on the level of water cooling Δ T w and cooling efficiency ε were also found. In the case of Δ T w , the effect is in the order of 0.1 – 0.2 ° C and results from the change in cooling water temperature and the heat exchange in the condenser. The ε value is influenced by air temperature and humidity, which determine the wet bulb temperature value. Within the range of power changes of the unit from 400 to 900 MWe , the evaporated water stream m ˙ e v , depending on the environmental conditions, increases from 400 – 600 tons / h to the value of 1000 – 1400 tons / h . It was determined that in the case of the average power of the unit at the level of 576.6 MWe , the average values of the evaporation and drift streams were respectively 0.78 % and 0.15 % of the cooling water stream. Using statistical methods, it was found that the influence of wind on the level of water cooling, cooling efficiency and cooling water losses was statistically significant.
Keywords: cooling tower; ambient conditions; water loss; power plant (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2021
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
https://www.mdpi.com/1996-1073/14/19/6412/pdf (application/pdf)
https://www.mdpi.com/1996-1073/14/19/6412/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:14:y:2021:i:19:p:6412-:d:651315
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().