Calculation Method of Allowable Continuous Current for Direct Burial Laying HVDC Underground Cable
Kyu-hoon Park,
Il Kwon and
Bang-wook Lee
Additional contact information
Kyu-hoon Park: HVDC Electric Power Laboratory, Department of Electronic Engineering, Hanyang University, Ansan 15588, Korea
Il Kwon: HVDC Electric Power Laboratory, Department of Electronic Engineering, Hanyang University, Ansan 15588, Korea
Bang-wook Lee: HVDC Electric Power Laboratory, Department of Electronic Engineering, Hanyang University, Ansan 15588, Korea
Energies, 2021, vol. 14, issue 19, 1-16
Abstract:
The calculation of the continuous allowable current of an underground cable is determined by various characteristics. To calculate the allowable current in cables with alternating magnetic fields such as AC, special phenomena such as the proximity effect and skin effect must be applied. However, there are no standards or research related to the calculation of the continuous allowable current of a DC power cable that does not have an alternating magnetic field. In this paper, a quantitative DC cable continuous allowable current calculation formula of direct burial laying was derived by applying the existing AC cable continuous allowable current calculation method to the DC system. We developed a calculation tool that can calculate the continuous allowable current of DC cables using the derived formula. Assuming the cable conditions (cable specification, laying conditions, soil characteristics, arrangement, and number of strands, etc.), a continuous allowable current simulation of DC cables was performed. In addition, the level of contribution to the continuous allowable current value was analyzed by classifying the parameter categories into major and minor factors in the order of influence on the allowable current among the determined calculated parameters. As a result, the effectiveness of the DC cable continuous allowable current calculation tool derived by performing the allowable current calculation simulation was evaluated, and the allowable current calculation method of the HVDC cable was established.
Keywords: allowable current; HVDC underground cable; direct burial laying; thermal resistance (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2021
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (3)
Downloads: (external link)
https://www.mdpi.com/1996-1073/14/19/6431/pdf (application/pdf)
https://www.mdpi.com/1996-1073/14/19/6431/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:14:y:2021:i:19:p:6431-:d:651794
Access Statistics for this article