The Use of a Real-Time Simulator for Analysis of Power Grid Operation States with a Wind Turbine
Zbigniew Kłosowski and
Sławomir Cieślik
Additional contact information
Zbigniew Kłosowski: Faculty of Telecommunications, Computer Science and Electrical Engineering, UTP University of Science and Technology, Kaliskiego 7, PL-85-796 Bydgoszcz, Poland
Sławomir Cieślik: Faculty of Telecommunications, Computer Science and Electrical Engineering, UTP University of Science and Technology, Kaliskiego 7, PL-85-796 Bydgoszcz, Poland
Energies, 2021, vol. 14, issue 8, 1-27
Abstract:
The main issue in this paper is the real-time simulator of a part of a power grid with a wind turbine. The simulator is constructed on the basis of a classic PC running under a classic operating system. The proposed solution is expected and desired by users who intend to manage power microgrids as separate (but not autonomous) areas of common national power systems. The main reason for the decreased interest in real-time simulators solutions built on the basis of PC is the simulation instability. The instability of the simulation is due to not keeping with accurate results when using small integration steps and loss of accuracy or loss of stability when using large integration steps. The second obstacle was due to the lack of a method for integrating differential equations, which gives accurate results with a large integration step. This is the scientific problem that is solved in this paper. A new solution is the use of a new method for integrating differential equations based on average voltage in the integration step (AVIS). This paper shows that the applied AVIS method, compared to other methods proposed in the literature (in the context of real-time simulators), allows to maintain simulation stability and accurate results with the use of large integration steps. A new (in the context of the application of the AVIS method) mathematical model of a power transformer is described in detail, taking into account the nonlinearity of the magnetization characteristics. This model, together with the new doubly-fed induction machine model (described in the authors’ previous article), was implemented in PC-based hardware. In this paper, we present the results of research on the operation states of such a developed real-time simulator over a long period (one week). In this way, the effectiveness of the operation of the real-time simulator proposed in the paper was proved.
Keywords: power network simulation; real-time simulation; mathematical modeling of power systems; average voltages in the integration step method (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2021
References: View references in EconPapers View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/14/8/2327/pdf (application/pdf)
https://www.mdpi.com/1996-1073/14/8/2327/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:14:y:2021:i:8:p:2327-:d:539705
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().