EconPapers    
Economics at your fingertips  
 

Cooling Performance Enhancement of a 20 RT (70 kW) Two-Evaporator Heat Pump with a Vapor–Liquid Separator

Won-Suk Yang and Young Il Kim
Additional contact information
Won-Suk Yang: Department of Architectural Engineering, Graduate School, Seoul National University of Science and Technology, Seoul 01811, Korea
Young Il Kim: School of Architecture, Seoul National University of Science and Technology, Seoul 01811, Korea

Energies, 2022, vol. 15, issue 11, 1-18

Abstract: 20 RT (70 kW) two-evaporator heat pump system was developed, manufactured, and tested to enhance the cooling performance using a vapor–liquid separator. In the proposed system, two evaporators are connected in series, and the refrigerant passing through the primary evaporator is separated into vapor and liquid using a vapor–liquid separator. The vapor refrigerant is passed to the compressor, whereas the liquid phase flows into the second evaporator. The amount of vapor refrigerant sent to the compressor can be adjusted through a needle valve opening (0%, 50%, and 100%). The influence of this parameter on the cooling performance was analyzed. The cooling performance tests were repeated five times to check repeatability. Data associated with the air and refrigerant sides were obtained, and the average coefficients of performance (COPs) were calculated. The average COP associated with the air side was approximately 5% lower than that pertaining to the refrigerant side owing to the heat loss. In terms of the air-side cooling performance, the average COP was 3.14, 3.40, and 3.68 when the valve openings were 0%, 50%, and 100%, respectively. The cooling performance when the valve opening was 100% was 17.2% higher than that for the valve opening of 0%. The findings demonstrated that the cooling performance of a heat pump can be enhanced using two evaporators and a vapor–liquid separator.

Keywords: COP; heat pump; cooling; two-evaporator; refrigerant; vapor–liquid separator (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2022
References: View references in EconPapers View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/1996-1073/15/11/3849/pdf (application/pdf)
https://www.mdpi.com/1996-1073/15/11/3849/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:15:y:2022:i:11:p:3849-:d:822436

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:15:y:2022:i:11:p:3849-:d:822436