A Novel Hardware-in-the-Loop Approach to Investigate the Impact of Low System Inertia on RoCoF Relay Settings
Peter Imris,
Gareth A. Taylor (),
Martin E. Bradley and
Yun Li
Additional contact information
Peter Imris: Department of Electronic and Electrical Engineering, Brunel University London, Uxbridge UB8 3PH, UK
Gareth A. Taylor: Department of Electronic and Electrical Engineering, Brunel University London, Uxbridge UB8 3PH, UK
Martin E. Bradley: Department of Electronic and Electrical Engineering, Brunel University London, Uxbridge UB8 3PH, UK
Yun Li: National Grid Electricity System Operator, St. Catherine’s Lodge, Wokingham RG41 5BN, UK
Energies, 2022, vol. 15, issue 17, 1-23
Abstract:
This paper presents a novel hardware-in-the-loop (HIL) approach as used to investigate the impact of the reduction in inertia on the Great Britain (GB) electrical power system with regard to rate of change of frequency (RoCoF) settings for Loss-of-Mains (LoM) protection. Furthermore, the research as presented in this paper updates, enhances, and validates a reduced model of the Great Britain transmission system, as originally developed in DIgSILENT PowerFactory by the National Grid Electricity System Operator. The enhanced model has been developed for integrated use with the OPAL-RT real-time HIL simulation toolkit and is validated against phasor measurement unit (PMU) data from actual disturbance events using novel automated interfacing between both integrated simulation platforms, PowerFactory from DIgSILENT and ePHASORSIM from OPAL-RT. The corresponding simulations show that the updated reduced model is capable of capturing the dynamic behaviour of the GB transmission system, including both local and inter-area oscillations, with satisfactory accuracy. Finally, the paper presents HIL study results with the reduced model to investigate the influence of decreasing system inertia on the response of LoM protection relays. The studies show that decreasing system inertia may have a significant impact on LoM relays using RoCoF detection, particularly relays using the legacy G59 setting of 0.125 Hz/s. Initial studies have also demonstrated the potential for a previously unrecognised interaction between system oscillations and the 500 ms operating delay, as specified in G59 and G99 Engineering Recommendations. Consequently, faster local oscillations (>1 Hz) reset the relay and decrease the sensitivity, whereas slower inter-area oscillations (<1 Hz) appear to cause the relay to overestimate the average RoCoF.
Keywords: rate of change of frequency; loss of mains; system inertia; reduced model; hardware-in-the-loop (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2022
References: View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/15/17/6386/pdf (application/pdf)
https://www.mdpi.com/1996-1073/15/17/6386/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:15:y:2022:i:17:p:6386-:d:903894
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().