An Experimental Investigation of Increasing the Thermal Efficiency of a Finned Tube Heat Exchanger by Using the Chimney Effect
Mikołaj Matuszczak () and
Sławomir Pietrowicz
Additional contact information
Mikołaj Matuszczak: Department of Air Conditioning, Heating, Gas Engineering and Air Protection, Faculty of Environmental Engineering, Wrocław University of Science and Technology, Wybrzeże Wyspiańskiego 27 St., 50-370 Wrocław, Poland
Sławomir Pietrowicz: Department of Thermodynamics and Renewable Energy Sources, Faculty of Mechanical and Power Engineering, Wrocław University of Science and Technology, Wybrzeże Wyspiańskiego 27 St., 50-370 Wrocław, Poland
Energies, 2022, vol. 15, issue 19, 1-16
Abstract:
In the paper, experimental analyses of the free convection heating transfer in a flat wavy-fin heat exchanger with the dimensions of 500 × 500 mm were investigated. The experimental reserch mainly included determining the average heat flux and heat-transfer coefficient for two selected types of finned heat exchangers. First, tests were conducted for exchangers without considering the so-called ’chimney’ effect; these tests will be treated as reference studies. Then, experiments for specially designed ’chimneys’ over the exchanger with heights of 350, 850, and 1350 mm, respectively, were carried out again. The analyses were performed for an average temperature difference between the heat-exchange surface and the environment in the range of 18 to 55 K. The experimental results demonstrated that, compared to the exchanger without a chimney, the addition of a chimney significantly affects the improvement in the thermal performance of the heat exchanger under natural convection conditions. Regarding the variant without a chimney, when a chimney is used with the highest height of 1350 mm and a maximum temperature difference of 55 K, the average heat flux increases by approximately 450% and the average heat-transfer coefficient is approximately 10 times higher. The heat exchanger characterised by lower airflow resistance showed higher values of average heat flux of 5 to 45% in the Rayleigh number range of 25 to 180. Studies have indicated that in some cases, a simple modification of the geometry of the heat exchanger leads to significant improvements in thermal performance and, in extreme cases, to the elimination of supporting equipment such as fans.
Keywords: natural convection; finned-tube heat exchangers; chimney effect (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2022
References: View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/15/19/7310/pdf (application/pdf)
https://www.mdpi.com/1996-1073/15/19/7310/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:15:y:2022:i:19:p:7310-:d:933770
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().