Energy Saving Evaluation with Low Liquid to Gas Ratio Operation in HVAC&R System
Ju-wan Ha,
Yu-jin Kim,
Kyung-soon Park and
Young-hak Song ()
Additional contact information
Ju-wan Ha: School of Architecture, College of Design, North Carolina State University, Raleigh, NC 27695, USA
Yu-jin Kim: Department of Architectural Engineering, Graduate School, Gyeongsang National University, Jinju 52828, Korea
Kyung-soon Park: Architectural Engineering Major, Division of Urban, Architecture and Civil Engineering, Dong-Eui University, Busan 47340, Korea
Young-hak Song: Department of Architectural Engineering, ERI, Gyeongsang National University, Jinju 52828, Korea
Energies, 2022, vol. 15, issue 19, 1-29
Abstract:
Previous studies have been conducted by employing various methods to reduce the condenser water temperature, a crucial control variable to consider when attempting to improve the operational efficiency of a chiller. The existing literature dealing with the effects of low-condenser water temperatures is limited, as the cooling water flow rate is often considered the operating variable of the condenser loop. However, to produce additional low condenser water temperatures, the approach temperature of the cooling tower in the system must be reduced. To reduce the approach temperature, it is necessary to review the physical behavior and efficiency of the cooling tower according to the change in the liquid to gas ratio (LGR), which is dependent upon the condenser water flow rate and the cooling tower fan air flow rate within the condenser loop. However, this process has rarely been reviewed in previous studies. Therefore, this study developed a new cooling tower control algorithm from the LGR perspective, and the operational effectiveness was quantitatively reviewed using EnergyPlus. Compared to the conventional conditions, when the cooling tower operation algorithm for low-approach temperatures was applied, the annual energy saving was 27.0%, the average chiller COP was improved by 27.8%, and the average system COP was improved by 47.4%. Furthermore, even when the algorithm was not applied at the same condenser water set temperature, the annual energy saving was 15%. The average COP of the chiller and COP of the system is improved by 2% and 23.2%, respectively. These results indicated that when a cooling tower is operated with a low LGR, even under the same outdoor air and load conditions, the cooling system’s efficiency can be improved with a change in the control algorithm without installing additional high-efficiency equipment.
Keywords: liquid–gas ratio (LGR); low-approach temperature; central chilled water system; efficiency improvement; cooling tower operation control; condenser water temperature; co-simulation; EnergyPlus (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2022
References: View references in EconPapers View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/15/19/7327/pdf (application/pdf)
https://www.mdpi.com/1996-1073/15/19/7327/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:15:y:2022:i:19:p:7327-:d:934151
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().