Analysis of a Costly Fiberglass-Polyester Air Filter Fire
Torgrim Log () and
Amalie Gunnarshaug
Additional contact information
Torgrim Log: Fire Disasters Research Group, Department of Safety, Chemistry and Biomedical Laboratory Sciences, Western Norway University of Applied Sciences, 5528 Haugesund, Norway
Amalie Gunnarshaug: Q Rådgivning AS, Øvregata 126, 5527 Haugesund, Norway
Energies, 2022, vol. 15, issue 20, 1-16
Abstract:
In September 2020, a fire at a liquefied natural gas (LNG) plant in the Arctic areas of Norway received national attention. In an unengaged air intake, the heat exchanger designed to prevent ice damage during production mode, was supplied hot oil at 260 °C. In sunny weather, calm conditions, and 14 °C ambient temperature, overheating of the unengaged air intake filters (85% glass fiber and 15% polyester) was identified as a possible cause of ignition. Laboratory heating tests showed that the filter materials could, due to the rigid glass fibers carrying the polymers, glow like smoldering materials. Thus, self-heating as observed for cellulose-based materials was a possible ignition mechanism. Small-scale testing (10 cm × 10 cm and 8 cm stacked height) revealed that used filters with collected biomass, i.e., mainly pterygota, tended to self-heat at 20 °C lower temperatures than virgin filters. Used filter cassettes (60 cm by 60 cm and 50 cm bag depth) caused significant self-heating at 150 °C. At 160 °C, the self-heating took several hours before increased smoke production and sudden transition to flaming combustion. Since the engaged heat exchanger on a calm sunny day of ambient temperature 14 °C would result in temperatures in excess of 160 °C in an unengaged air intake, self-heating and transition to flaming combustion was identified as the most likely cause of the fire. Flames from the burning polymer filters resulted in heat exchanger collapse and subsequent hot oil release, significantly increasing the intensity and duration of the fire. Due to firewater damages, the plant was out of operation for more than 1.5 years. Better sharing of lessons learned may help prevent similar incidents in the future.
Keywords: polyester air filter; pterygota; self-heating; hot oil; industry fire; air intake fire (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2022
References: View references in EconPapers View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/15/20/7719/pdf (application/pdf)
https://www.mdpi.com/1996-1073/15/20/7719/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:15:y:2022:i:20:p:7719-:d:947004
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().