Determination of the Interzonal Airflows in Naturally Ventilated Dwellings Based on Concentration Measurements of the Metabolic Carbon Dioxide
Anna Bulińska and
Zbigniew Buliński ()
Additional contact information
Anna Bulińska: Department of Heating, Ventilation and Dust Removal, Silesian University of Technology, 44-100 Gliwice, Poland
Zbigniew Buliński: Department of Thermal Technology, Silesian University of Technology, 44-100 Gliwice, Poland
Energies, 2022, vol. 16, issue 1, 1-19
Abstract:
The role of interzonal airflows is especially pronounced in naturally ventilated buildings. In such buildings, reversed airflows in the ventilation stacks might occur as well. This affects the air exchange rate and contaminant distribution in buildings. A significant increase in carbon dioxide concentration is a characteristic phenomenon for poorly ventilated rooms. This paper demonstrates the application of metabolic carbon dioxide concentration measurements for interzonal airflow estimation in naturally ventilated buildings. The presented method is based on the continuous measurements of CO 2 concentration at one point in each zone. These measurements are used to estimate airflow pattern in a multizone building by applying an inverse analysis. The developed methodology employs an iterative Levenberg-Marquardt procedure to maximise the nonlinear likelihood function. The validity of the method was verified against measurements carried out in a single naturally ventilated room. Further, the method was applied to calculate the airflow pattern in two apartments in Poland, containing 4 and 6 zones. The obtained results revealed very poor ventilation in both investigated apartments and reversed airflow in exhaust ducts. The amount of fresh air entering the rooms was insufficient to ensure good indoor air quality. The developed methodology can be effectively used as a diagnostic tool to identify the potential problems with ventilation systems.
Keywords: natural ventilation; interzonal airflows; tracer gas method; carbon dioxide; indoor air quality; inverse analysis (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2022
References: View references in EconPapers View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/16/1/95/pdf (application/pdf)
https://www.mdpi.com/1996-1073/16/1/95/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:16:y:2022:i:1:p:95-:d:1010767
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().