Virtual Armature Resistance-Based Control for Fault Current Limiting in a High-Order VSG and the Impact on Its Transient Stability
Daniel Carletti,
Thiago Amorim and
Lucas Encarnação ()
Additional contact information
Daniel Carletti: Department of Electrical Engineering, Federal University of Espírito Santo (UFES), Av. Fernando Ferrari, 514, Vitória 29075-910, Brazil
Thiago Amorim: Department of Electrical Engineering, Federal University of Espírito Santo (UFES), Av. Fernando Ferrari, 514, Vitória 29075-910, Brazil
Lucas Encarnação: Department of Electrical Engineering, Federal University of Espírito Santo (UFES), Av. Fernando Ferrari, 514, Vitória 29075-910, Brazil
Energies, 2023, vol. 16, issue 12, 1-16
Abstract:
This article proposes a fault ride through (FRT) technique for a high-order virtual synchronous generator (VSG) that adjusts its virtual armature resistance. When a fault is detected by a dedicated algorithm, the proposed control adjusts the resistance parameter accordingly. The main contribution of this article is to adjust the virtual resistance directly in the machine model to limit the current during faults, unlike other techniques proposed in the literature that add another control loop to produce the virtual impedance effects. To validate the effectiveness of the proposed control, a hardware-in-the-loop real-time simulation platform was adopted using a Typhoon HIL 402 device and a Texas Instruments F28379D digital controller. The results demonstrate that the control effectively limits the converter’s current while still contributing to raising the system’s critical clearing time (CCT) and improving transient stability. The proposed FRT strategy is validated in a three-phase fault scenario in which a 500 kVA–480 V converter’s peak fault current is reduced from 5 kA to 1.4 kA, depending on the resistance value adjusted. The transient stability is also analyzed in 30 different scenarios and the VSG support on the CCT is reduced by 23 ms on average. However, when compared to the baseline scenario without the VSG, the system still sees an increase in CCT with the current limiting control applied. Additionally, the control allows the VSG to smoothly transition to island mode in a scenario where the fault is cleared and the grid is disconnected by a protection system.
Keywords: fault ride through; grid-forming converter; power system stability; transient stability; virtual synchronous generator (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2023
References: View references in EconPapers View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/16/12/4680/pdf (application/pdf)
https://www.mdpi.com/1996-1073/16/12/4680/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:16:y:2023:i:12:p:4680-:d:1169854
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().