EconPapers    
Economics at your fingertips  
 

Operation Mode and Energy Consumption Analysis of a New Energy Tower and Ground Source-Coupled Heat Pump System

Yao Zhang, Ronghua Wu (), Hao Yu, Yujuan Yang and Hao Zhan
Additional contact information
Yao Zhang: College of Mechanical and Electrical Engineering, Qingdao University, Qingdao 266071, China
Ronghua Wu: College of Mechanical and Electrical Engineering, Qingdao University, Qingdao 266071, China
Hao Yu: Qingdao KC Blue New Energy Co., Ltd., Qingdao 266300, China
Yujuan Yang: College of Mechanical and Electrical Engineering, Qingdao University, Qingdao 266071, China
Hao Zhan: Qingdao KC Blue New Energy Co., Ltd., Qingdao 266300, China

Energies, 2023, vol. 16, issue 18, 1-20

Abstract: In order to solve the problems of performance degradation in energy tower heat pump (ETHP) systems under low temperature conditions and soil heat imbalances in ground source heat pump (GSHP) systems in cold regions, a new coupled system of ETHP and GSHP systems (the ET–GSHP system) and its operating mode were proposed. The mathematical model of the system was constructed along with the system’s form and operation scheme. The COP (coefficient of performance) and total energy consumption of the coupled system were then simulated and studied under a number of common operating situations. The heating season is divided into four periods based on varying outdoor ambient temperatures: the first period operates in series mode and has an average outdoor temperature of 2.38 °C; the second period operates in parallel mode and has an average outdoor temperature of −8.56 °C; the third period uses soil source heat pumps to operate separately; and the fourth period operates in series mode and has an average outdoor temperature of −11.32 °C. Operation of the coupled system in four periods was simulated and analyzed, and the operational efficiency and energy saving of the system were analyzed using an actual commercial building in a cold region as an example. The results demonstrate that the ET–GSHP system’s overall energy consumption during the heating period is reduced by 4.34% when compared to the traditional GSHP systems; the system’s COP can maintain a high level throughout the heating period, with an average COP of 3.315; and the soil temperature at the conclusion of the heating period is 25 °C, which is 8.89 °C higher than that of the traditional GSHP system, providing a guarantee of summer heat return. The new ET–GSHP system significantly boosts the efficiency of the system’s operation, achieves effective coupling between various heat sources through multi-stage control, and offers improved energy-saving advantages.

Keywords: energy tower; ground source heat pump; coupled system; energy consumption analysis (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2023
References: View references in EconPapers View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/1996-1073/16/18/6493/pdf (application/pdf)
https://www.mdpi.com/1996-1073/16/18/6493/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:16:y:2023:i:18:p:6493-:d:1235959

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:16:y:2023:i:18:p:6493-:d:1235959