A New Method of Fault Localization for 500 kV Transmission Lines Based on FRFT-SVD and Curve Fitting

Mohamed H. Saad (), Mostafa M. Fouda () and Abdelrahman Said
Additional contact information
Mohamed H. Saad: Radiation Engineering Department, National Center for Radiation Research and Technology (NCRRT), Egyptian Atomic Energy Authority, Cairo 11672, Egypt
Mostafa M. Fouda: Department of Electrical and Computer Engineering, College of Science and Engineering, Idaho State University, Pocatello, ID 83209, USA
Abdelrahman Said: Department of Electrical Engineering, Faculty of Engineering at Shoubra, Benha University, Cairo 11672, Egypt

Energies, 2023, vol. 16, issue 2, 1-23

Abstract: The paper presents the Fractional Fourier Transform-Singular Value Decomposition (FRFT-SVD) method for the localization of various power system faults in a 200 km long, 500 kV Egyptian transmission line using sent end-line current signals. Transient simulations are carried out using Alternating Transient Program/Electromagnetic Transient Program (ATP-EMTP), and the outcomes are then examined in MATLAB to carry out a sensitivity analysis against measurement noises, sampling frequency, and fault characteristics. The proposed work employs current fault signals of five distinct kinds at nineteen intermediate points throughout the length of the line. The approach utilized to construct the localizer model is FRFT-SVD. It is much more effortless, precise, and effective. The FRFT-SVD is utilized in this technique to calculate 19 sets of indices of the greatest S value throughout the length of the line. The FRFT-SVD localizer model is also designed to be realistic, with power system noise corrupting fault signals. To generate fault curves, the curve fitting technique is applied to these 19 sets of indices. Reduced chi-squared and modified R-squared criteria are used to choose the best-suited curve. The proposed work results in a very precise localization, with only a 0.0016% average percentage error for fault localization and a maximum percentage error of 0.002% for the 200 km Egyptian transmission line. Finally, this work can be employed as a proper link between the nuclear power plant and the grid. The proposed method is an efficient fault distance estimation method that might contribute to creating a dependable transient-based approach to power system protection.

Keywords: fault location; ATP-EMTP; long transmission line; curve fitting techniques; FRFT-SVD (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2023
References: View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/1996-1073/16/2/758/pdf (application/pdf)
https://www.mdpi.com/1996-1073/16/2/758/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:16:y:2023:i:2:p:758-:d:1029744

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:16:y:2023:i:2:p:758-:d:1029744