Novel Harmonic Distortion Prediction Methods for Meshed Transmission Grids with Large Amount of Underground Cables
Vladislav Akhmatov (),
Bjarne Søndergaard Bukh,
Chris Liberty Skovgaard and
Bjarne Christian Gellert
Additional contact information
Vladislav Akhmatov: Energinet, Transmission System Operator of Denmark, 7000 Fredericia, Denmark
Bjarne Søndergaard Bukh: Energinet, Transmission System Operator of Denmark, 7000 Fredericia, Denmark
Chris Liberty Skovgaard: Energinet, Transmission System Operator of Denmark, 7000 Fredericia, Denmark
Bjarne Christian Gellert: Energinet, Transmission System Operator of Denmark, 7000 Fredericia, Denmark
Energies, 2023, vol. 16, issue 9, 1-39
Abstract:
The tremendous and fast green transition in Denmark has initiated the large-scale grid-integration of renewable energy sources, electrification of energy consumption, and establishment of PtX and Energy Islands, setting goals for transmission grid development—such as the establishment of new connections—and for grid reconstruction—such as the extensive substitution of overhead lines (OHLs) with underground cables (UGCs). The share of UGCs in the Danish transmission grid is increasing. Presence of UGC has resulted in that resonances of the harmonic impedance characteristics of the transmission grid are brought within the harmonic order range coinciding with the harmonic emission sources and causing systemwide increase of the harmonic voltage distortion in the 400 kV transmission grid. The transformation of the 400 kV transmission grid has given rise to the need to predict harmonic voltage distortion using simulation models to secure an adequate power quality and support investment decisions and harmonic mitigation for the grid stage, which has not yet been established and which differs from the present grid. This paper presents the experiences of Energinet, the Transmission System Operator (TSO) in Denmark, with harmonic distortion in the Danish transmission grid due to the establishment of 400 kV UGCs, and the development of measurement-validated methods for harmonic distortion simulation and prediction. The paper also presents ongoing developments within, and research addressing, the prediction of harmonic distortion in meshed grids; for example, it explores where and how an analytical approach can replace observational studies with many numerical simulations. The methods shall make it possible to predict whether, where in the transmission grid, and for which harmonic orders connections that have not yet been commissioned may cause the violation of the planning levels, and which mitigations are necessary for bringing the harmonic distortion below the planning levels with respect to a given margin.
Keywords: harmonic assessment; harmonic distortion; harmonic impedance; meshed grid; method; harmonic voltage measurement; statistical method; underground cables; simulation; validation (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2023
References: View references in EconPapers View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/16/9/3965/pdf (application/pdf)
https://www.mdpi.com/1996-1073/16/9/3965/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:16:y:2023:i:9:p:3965-:d:1142146
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().