EconPapers    
Economics at your fingertips  
 

Generation and Validation of CFD-Based ROMs for Real-Time Temperature Control in the Main Control Room of Nuclear Power Plants

Seung-Hoon Kang, Dae-Kyung Choi, Sung-Man Son and Choengryul Choi ()
Additional contact information
Seung-Hoon Kang: ELSOLTEC, #1401-2, BLDG A, 184, Jungbu-daero, Giheung-gu, Yongin-si 17095, Gyeonggi-do, Republic of Korea
Dae-Kyung Choi: ELSOLTEC, #1401-2, BLDG A, 184, Jungbu-daero, Giheung-gu, Yongin-si 17095, Gyeonggi-do, Republic of Korea
Sung-Man Son: ELSOLTEC, #1401-2, BLDG A, 184, Jungbu-daero, Giheung-gu, Yongin-si 17095, Gyeonggi-do, Republic of Korea
Choengryul Choi: ELSOLTEC, #1401-2, BLDG A, 184, Jungbu-daero, Giheung-gu, Yongin-si 17095, Gyeonggi-do, Republic of Korea

Energies, 2024, vol. 17, issue 24, 1-21

Abstract: This study develops and validates a Reduced Order Model (ROM) integrated with Digital Twin technology for real-time temperature control in the Main Control Room (MCR) of a nuclear power plant. Utilizing Computational Fluid Dynamics (CFD) simulations, we obtained detailed three-dimensional thermal flow distributions under various operating conditions. A ROM was generated using machine learning techniques based on 94 CFD cases, achieving a mean temperature error of 0.35%. The ROM was further validated against two excluded CFD cases, demonstrating high correlation coefficients (R > 0.84) and low error metrics, confirming its accuracy and reliability. Integrating the ROM with the Heating, Ventilating, and Air Conditioning (HVAC) system, we conducted a two-month simulation, showing effective maintenance of MCR temperature within predefined criteria through adaptive HVAC control. This integration significantly enhances operational efficiency and safety by enabling real-time monitoring and control while reducing computational costs and time associated with full-scale CFD analyses. Despite promising results, the study acknowledges limitations related to ROM’s dependency on training data quality and the need for more comprehensive validation under diverse and unforeseen conditions. Future research will focus on expanding the ROM’s applicability, incorporating advanced machine learning methods, and conducting pilot tests in actual nuclear plant environments to further optimize the Digital Twin-based control system.

Keywords: reduced order model; computational fluid dynamics; real-time temperature control; HVAC system; nuclear power plant main control room; digital twin (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2024
References: View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/1996-1073/17/24/6406/pdf (application/pdf)
https://www.mdpi.com/1996-1073/17/24/6406/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:17:y:2024:i:24:p:6406-:d:1547839

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:17:y:2024:i:24:p:6406-:d:1547839