Research on Opening Reignition Characteristics and Suppression Measures of 750 kV AC Filter Circuit Breakers

Jianguo Zhang, Pengcheng Sha, Feiyue Ma, Bo Niu, Xu Cai, Hui Ni and Junbo Deng ()
Additional contact information
Jianguo Zhang: State Grid Ningxia Electric Power Research Institute, Yinchuan 750001, China
Pengcheng Sha: State Key Lab of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China
Feiyue Ma: State Grid Ningxia Electric Power Research Institute, Yinchuan 750001, China
Bo Niu: State Grid Ningxia Electric Power Research Institute, Yinchuan 750001, China
Xu Cai: State Key Lab of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China
Hui Ni: State Grid Ningxia Electric Power Research Institute, Yinchuan 750001, China
Junbo Deng: State Key Lab of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China

Energies, 2025, vol. 18, issue 1, 1-18

Abstract: The operation of converter valves in converter stations often results in high reactive power consumption and harmonic generation, necessitating measures to maintain reactive power balance and ensure power quality. To achieve this, the filter bank circuit breaker is frequently switched on and off during daily operation. In recent years, multiple incidents of circuit breaker breakdown during the opening process have been reported. In this study, power systems computer-aided design (PSCAD)/electromagnetic transients including DC (EMTDC) V5.0 electromagnetic transient simulation software is used to simulate and calculate the overvoltage and inrush current under different configurations of circuit breaker operating mechanism dispersion, opening phase angle, and operating speed. Additionally, the suppression effects of two measures are compared: “phase selection opening” and “phase selection opening combined with controlled opening speed” to mitigate overvoltage and inrush current. The results demonstrate that for BP11/13 filters, HP24/36 filters, and HP3 filters, the combined strategy of “phase-selective opening with controlled opening speed” is more effective in suppressing inrush current and overvoltage. However, for SC filters, the suppression effect of this combined strategy is not significant. Considering economic and practical factors, it is more reasonable to adopt the phase-selective opening measure for SC filters. These findings provide guidance for ensuring the safe operation of AC filter circuit breakers.

Keywords: AC filter bank circuit breaker; arc model; open switch reignition; opening speed; opening phase angle (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2025
References: View references in EconPapers View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/1996-1073/18/1/218/pdf (application/pdf)
https://www.mdpi.com/1996-1073/18/1/218/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:18:y:2025:i:1:p:218-:d:1561176

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:18:y:2025:i:1:p:218-:d:1561176