Integrated Soil Temperature Measurement at Multiple Depths for Building Energy Performance Assessment Under Climate Change Conditions
Ewa Daniszewska,
Aldona Skotnicka-Siepsiak (),
Anna Górska-Pawliczuk and
Piotr E. Srokosz
Additional contact information
Ewa Daniszewska: Faculty of Geoengineering, University of Warmia and Mazury in Olsztyn, 10-724 Olsztyn, Poland
Aldona Skotnicka-Siepsiak: Faculty of Geoengineering, University of Warmia and Mazury in Olsztyn, 10-724 Olsztyn, Poland
Anna Górska-Pawliczuk: Faculty of Geoengineering, University of Warmia and Mazury in Olsztyn, 10-724 Olsztyn, Poland
Piotr E. Srokosz: Faculty of Geoengineering, University of Warmia and Mazury in Olsztyn, 10-724 Olsztyn, Poland
Energies, 2025, vol. 18, issue 22, 1-22
Abstract:
This article presents an original, multi-depth soil-temperature monitoring system based on TMP117 digital sensors designed for deployment at several depths. The objective was to evaluate the system’s accuracy and applicability for building-energy performance assessment under contemporary climate conditions. Urban measurements at depths between 1.0 and 2.0 m were compared with ground temperatures derived using PN-EN 16798-5-1:2017-07 with Typical Meteorological Year (TMY) inputs and with observations from the Polish Institute of Meteorology and Water Management (IMWM). Standard inputs underestimated soil temperature on average by 1.1–2.3 °C (TMY) and 2.0–2.8 °C (IMWM), with the bias increasing with depth. For a ground-to-air heat-exchanger (GAHE) assessment, energy benefits estimated from standard inputs were lower in measurements by approximately 30–60% for pre-cooling and 70–86% for pre-heating. Measurements also revealed location-dependent differences between boreholes attributable to underground infrastructure. These findings indicate that non-local or outdated climate datasets can materially overestimate GAHE potential and confirm the need for local, multi-depth ground measurements and periodic updates of standard climate inputs to reflect urbanized conditions and climate change. The presented system constitutes a practical, scalable tool for engineers and designers of HVAC systems relying on ground heat exchange.
Keywords: ground temperature; measurement systems; miniature sensors; ground-air heat exchanger (GAHE); building energy modeling; efficiency analysis (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2025
References: Add references at CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/18/22/5881/pdf (application/pdf)
https://www.mdpi.com/1996-1073/18/22/5881/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:18:y:2025:i:22:p:5881-:d:1790288
Access Statistics for this article
Energies is currently edited by Ms. Cassie Shen
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().