Differential Protection for an Outgoing Transformer of Large-Scale Doubly Fed Induction Generator-Based Wind Farms
Bingtuan Gao,
Wei Wei,
Luoma Zhang,
Ning Chen,
Yingjun Wu and
Yi Tang
Additional contact information
Bingtuan Gao: School of Electrical Engineering, Southeast University, No. 2, Sipailou, Nanjing 210096, Jiangsu, China
Wei Wei: School of Electrical Engineering, Southeast University, No. 2, Sipailou, Nanjing 210096, Jiangsu, China
Luoma Zhang: School of Electrical Engineering, Southeast University, No. 2, Sipailou, Nanjing 210096, Jiangsu, China
Ning Chen: China Electric Power Research Institute, No. 8, Nanrui Road, Nanjing 210003, Jiangsu, China
Yingjun Wu: School of Automation, Nanjing University of Posts and Telecommunications, No. 9, Wenyuan Road, Nanjing 210023, Jiangsu, China
Yi Tang: School of Electrical Engineering, Southeast University, No. 2, Sipailou, Nanjing 210096, Jiangsu, China
Energies, 2014, vol. 7, issue 9, 1-20
Abstract:
With the rapid development of wind energy, relay protection for large-scale wind farms has been attracting some researchers, due to the absence of standards. Based on the large-scale doubly fed induction generator (DFIG)-based wind farms located in Gansu Province, China, this paper studies the differential protection for the outgoing power transformer of large-scale DFIG-based wind farms. According to the equivalent circuit of the power grid integrated with wind farms, the main frequency components of current and voltage during faults are identified mathematically and then verified by simulations. The results show that the frequencies of current and voltage at the terminals of outgoing transmission lines are inconsistent. Following the feature of frequency inconsistency, the adaptability of differential protection is analyzed, and it is found that differential protection for an outgoing transformer in large-scale wind farms may fail once ignoring the frequency inconsistency. Simulation studies demonstrate that inconsistent frequency characteristics will deteriorate the sensitivity and reliability of differential protection. Finally, several suggestions are provided for improving the performance of relay protections for large-scale DFIG-based wind farms.
Keywords: wind farm; differential protection; transformer; frequency inconsistency (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2014
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (5)
Downloads: (external link)
https://www.mdpi.com/1996-1073/7/9/5566/pdf (application/pdf)
https://www.mdpi.com/1996-1073/7/9/5566/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:7:y:2014:i:9:p:5566-5585:d:39611
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().