Ultrafine and Fine Particulate Matter Inside and Outside of Mechanically Ventilated Buildings
Shelly L. Miller,
Nick A. Facciola,
Darin Toohey and
John Zhai
Additional contact information
Shelly L. Miller: Department of Mechanical Engineering; University of Colorado, Boulder, CO 80309, USA
Nick A. Facciola: Department of Mechanical Engineering; University of Colorado, Boulder, CO 80309, USA
Darin Toohey: Department of Atmospheric and Oceanic Sciences, University of Colorado, Boulder, CO 80309, USA
John Zhai: Department of Civil, Environmental and Architectural Engineering, University of Colorado, Boulder, CO 80309, USA
IJERPH, 2017, vol. 14, issue 2, 1-17
Abstract:
The objectives of this study were to measure levels of particulate matter (PM) in mechanically ventilated buildings and to improve understanding of filtration requirements to reduce exposure. With the use of an Ultra High Sensitivity Aerosol Spectrometer and an Aerodyne Mass Spectrometer, ultrafine (0.055–0.1 ?m) and fine (0.1–0.7 ?m) indoor and outdoor PM was measured as a function of time in an office, a university building, and two elementary schools. Indoor particle levels were highly correlated with outdoor levels. Indoor and outdoor number concentrations in Denver were higher than those in Boulder, with the highest number concentrations occurring during summer and fall. The ratio of indoor-to-outdoor (I/O) PM was weakly but positively correlated with the amount of ventilation provided to the indoor environment, did not vary much with particle size (ranged between 0.48 and 0.63 for the entire size range), and was similar for each period of the week (weekend vs. weekday, night vs. day). Regression analyses showed that ultrafine indoor PM baseline concentrations were higher at night from nighttime infiltration. A lag time was observed between outdoor and indoor measurements. Weekday days had the shortest lag time of 11 min, and weekend nighttime lags when the HVAC was not in use were 50 to 148 min. Indoor-outdoor PM concentration plots showed ultrafine PM was more correlated compared to fine, and especially when the HVAC system was on. Finally, AMS data showed that most of the PM was organic, with occasional nitrate events occurring outdoors. During nitrate events, there were less indoor particles detected, indicating a loss of particulate phase nitrate. The results from this study show that improved filtration is warranted in mechanically ventilated buildings, particularly for ultrafine particles, and that nighttime infiltration is significant depending on the building design.
Keywords: aerosols; ultrafine particles; particle number count; infiltration; nitrate (search for similar items in EconPapers)
JEL-codes: I I1 I3 Q Q5 (search for similar items in EconPapers)
Date: 2017
References: View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1660-4601/14/2/128/pdf (application/pdf)
https://www.mdpi.com/1660-4601/14/2/128/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jijerp:v:14:y:2017:i:2:p:128-:d:89006
Access Statistics for this article
IJERPH is currently edited by Ms. Jenna Liu
More articles in IJERPH from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().