Effects of ERV Filter Degradation on Indoor CO 2 Levels of a Classroom
Jae-Sol Choi,
Jae-Hyuk Lee and
Eui-Jong Kim
Additional contact information
Jae-Sol Choi: Department of Architectural Engineering, Inha University, Incheon 22212, Korea
Jae-Hyuk Lee: Air Solution B2B Sales Engineering Team, LG Electronics, Seoul 07336, Korea
Eui-Jong Kim: Department of Architectural Engineering, Inha University, Incheon 22212, Korea
Sustainability, 2018, vol. 10, issue 4, 1-15
Abstract:
Energy recovery ventilators (ERVs) are widely used to reduce energy losses caused by ventilation and improve indoor air quality for recently-constructed buildings. It is important for spaces with high occupancy density and longer residence times, such as classrooms. In classrooms, the ERV size is typically estimated by the target number of students in the design phase, but the design air volume flow rates (m 3 /h) of the ERV can decrease over time owing to filter degradation such as increased dust loading. In this study, field tests are conducted in a classroom to investigate filter degradation through a visual inspection and by measuring the air volume flow rates at the diffusers connected to the ERV. In addition, variations in carbon dioxide (CO 2 ) concentrations are also measured to verify the effects of filter degradation on the indoor CO 2 levels over the entire test period, which includes filter replacement, as well. As the tests are conducted during classes, several adjusting methodologies are proposed to match the different test conditions. The results show that the total air volume flow rate of the ERV increases after the filter replacement (546 to 766 m 3 /h), but it again decreases as time elapses (659 m 3 /h). Accordingly, the indoor CO 2 concentration decreases after the filter replacement by more than 300 ppm (1404 to 1085 ppm), clearly showing the effect of filter degradation. However, this CO 2 concentration remains similar for four months after the replacement, and the total air volume rate decreases again. An interpretation is made using computational fluid dynamics analysis that the measured CO 2 concentrations are affected by airflow patterns. The airflow in the cooling system may dilute CO 2 concentrations at the measuring location. Thus, periodic filter replacement and management are important to ensure the desired ERV air volume rates and consequently the desired indoor CO 2 concentrations.
Keywords: filter degradation; CO 2 concentration; energy recovery ventilator (search for similar items in EconPapers)
JEL-codes: O13 Q Q0 Q2 Q3 Q5 Q56 (search for similar items in EconPapers)
Date: 2018
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
https://www.mdpi.com/2071-1050/10/4/1215/pdf (application/pdf)
https://www.mdpi.com/2071-1050/10/4/1215/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jsusta:v:10:y:2018:i:4:p:1215-:d:141475
Access Statistics for this article
Sustainability is currently edited by Ms. Alexandra Wu
More articles in Sustainability from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().