EconPapers    
Economics at your fingertips  
 

Non-Potable Water Quality Assessment Results for Water Conservation in the Context of a Medical Facility Case Study

Geraldine Seguela, John Richard Littlewood and George Karani
Additional contact information
Geraldine Seguela: Sustainable & Resilient Built Environment Research Group, Cardiff School of Art & Design, Cardiff Metropolitan University, Western Avenue, Cardiff CF5 2YB, UK
John Richard Littlewood: Sustainable & Resilient Built Environment Research Group, Cardiff School of Art & Design, Cardiff Metropolitan University, Western Avenue, Cardiff CF5 2YB, UK
George Karani: Environment & Public Health Research Group, Cardiff School of Health Sciences, Cardiff Metropolitan University, Western Avenue, Cardiff CF5 2YB, UK

Sustainability, 2022, vol. 14, issue 11, 1-26

Abstract: This paper discusses recycled non-potable water (NPW) quality test results from an existing, decentralized, treated air handling unit (AHU) air conditioning (A/C) condensate water (CW) system in a medical facility case study (MFCS) in Abu Dhabi (AD), the capital city of the United Arab Emirates (UAE). The MFCS, a 364-bed hospital that opened in 2015 with 50% landscaping, is targeting 100% non-clinical/non-potable water use for landscape irrigation (LI) from 179,700 m 3 /year treated CW, which is a by-product of AHU A/C. For seven months per year, however, a deficit of 14,340 m 3 AHU A/C CW occurs, so costly and non-sustainable, desalinated potable water is required. The proposed change project, using a mixed methodology, develops a sustainable NPW strategy, including a protocol to extract water from recycled, onsite, organic food waste, fire sprinkler pump test water (FSPTW), and reverse osmosis reject water (RORW) to meet the AHU A/C CW shortfall by adapting, enhancing, and monitoring the medical facility’s NPW treatment system. The hospital’s sustainability strategy implemented by the author could be legislated and mandated by the relevant authority for regional medical facilities, taking the form of a water conservation protocol including the classification and characterization of different types of NPW to understand their impact on LI, human health, and building water systems. The outcome is a novel change in practice to reuse 25,141 m 3 /year RORW and 1136 m 3 /year FSPTW as makeup water for the A/C CW shortfall in winter. The results identify key considerations to be addressed by the target audience (building owners, landscape contractors, and facility managers) when reusing NPW to protect the environment against soil degradation—a major aspect of decarbonization.

Keywords: water sustainability; wastewater; access to water; water scarcity (search for similar items in EconPapers)
JEL-codes: O13 Q Q0 Q2 Q3 Q5 Q56 (search for similar items in EconPapers)
Date: 2022
References: View references in EconPapers View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/2071-1050/14/11/6578/pdf (application/pdf)
https://www.mdpi.com/2071-1050/14/11/6578/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jsusta:v:14:y:2022:i:11:p:6578-:d:825791

Access Statistics for this article

Sustainability is currently edited by Ms. Alexandra Wu

More articles in Sustainability from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jsusta:v:14:y:2022:i:11:p:6578-:d:825791