Abstract:
A central air-conditioning (AC) system includes the chiller, chiller water pump, cooling water pump, cooling tower, and chilled water secondary pumps. Among these devices, the chiller consumes most power of the central AC system. In this paper, the adaptive neuro-fuzzy inference system (ANFIS) and genetic algorithm (GA) were utilized for optimizing the chiller loading. The ANFIS could construct a power consumption model of the chiller, reduce modeling period, and maintain the accuracy. GA could optimize the chiller loading for better energy efficiency. The simulating results indicated that ANFIS combined with GA could optimize the chiller loading. The power consumption was reduced by 6.32–18.96% when partial load ratio was located at the range of 0.6~0.95. The chiller power consumption model established by ANFIS could also increase the convergence speed. Therefore, the ANFIS with GA could optimize the chiller loading for reducing power consumption.
Date: 2015
References: Add references at CitEc
Citations: View citations in EconPapers (2)
Downloads: (external link)
http://downloads.hindawi.com/journals/MPE/2015/306401.pdf (application/pdf)
http://downloads.hindawi.com/journals/MPE/2015/306401.xml (text/xml)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:hin:jnlmpe:306401
DOI: 10.1155/2015/306401
Access Statistics for this article
More articles in Mathematical Problems in Engineering from Hindawi
Bibliographic data for series maintained by Mohamed Abdelhakeem ().