Grounding resistance measurement by grid electrode in Brunei Darussalam
Md. Abdus Salam
International Journal of Energy Technology and Policy, 2012, vol. 8, issue 2, 196-208
Abstract:
This paper presents soil resistivity and grounding resistance measurements. The measured soil resistivity is used as the input of CYME GRD software for simulation purpose. The rms error between the measured and the calculated ground resistivity is found to be 4.38%. The grounding resistances are measured by placing the electrode as single and double rectangular grids horizontally into the soil. A mathematical relationship between the grounding resistance and the related variables has been developed by employing dimensional analysis technique. The experimental result is used to find the dimensional and arc constants. The correlation coefficients for two cases have been determined and it is found that the grounding resistance is strongly correlated with the length of the buried electrode into the soil.
Keywords: soil resistivity; CYME GRD software; dimensional analysis; fall-of-potential method; rms error; Brunei Darussalam; grounding resistance measurement; grid electrodes; simulation. (search for similar items in EconPapers)
Date: 2012
References: Add references at CitEc
Citations:
Downloads: (external link)
http://www.inderscience.com/link.php?id=46568 (text/html)
Access to full text is restricted to subscribers.
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:ids:ijetpo:v:8:y:2012:i:2:p:196-208
Access Statistics for this article
More articles in International Journal of Energy Technology and Policy from Inderscience Enterprises Ltd