The numerical simulation and experimental study on rack cooling effect in date center with UFAD system
Yunzhi Ling,
Xiaosong Zhang,
Shuhong Li,
Guannan Han and
Xiaogeng Sun
International Journal of Low-Carbon Technologies, 2015, vol. 10, issue 4, 446-451
Abstract:
In order to analyze the way of improving the cooling effect of the data center with the UFAD system, the HVAC simulation software—Airpak—was applied. Numerical simulations for the interior temperature of the rack at different porosity ratios were carried out, and the simulated results indicate that the way of partly enhancing the porosity ratio of the front door and back door can improve the cooling effect. To solve the issue of the thermal current recycle in the exhaust outlet and airflow distribution disorder, the measure of the cold aisle regional closure was taken, and the comparison of data before and after the closure of the cold aisle proved its positive influence on the cooling effect: to lowering the inlet air temperature of racks, to improve airflow distribution inside and outside of the rack and to solve the thermal current recycle in the exhaust outlet.
Date: 2015
References: View complete reference list from CitEc
Citations: View citations in EconPapers (1)
Downloads: (external link)
http://hdl.handle.net/10.1093/ijlct/ctt011 (application/pdf)
Access to full text is restricted to subscribers.
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:oup:ijlctc:v:10:y:2015:i:4:p:446-451.
Access Statistics for this article
International Journal of Low-Carbon Technologies is currently edited by Saffa B. Riffat
More articles in International Journal of Low-Carbon Technologies from Oxford University Press
Bibliographic data for series maintained by Oxford University Press ().