EconPapers    
Economics at your fingertips  
 

Performance of an integrated solar absorption cooling system in a sub-tropical region

J. Darkwa and S. Fraser

International Journal of Low-Carbon Technologies, 2012, vol. 7, issue 3, 199-207

Abstract: Evaluation of an integrated solar absorption cooling system located in a sub-tropical region has been carried out. Analysis of the results revealed an operational efficiency of 61% for the solar collectors at a mean differential temperature of 51°C when compared with the manufacturer's rating of 70% at 60°C. The absorption chiller did, however, perform quite satisfactorily and achieved a coefficient of performance of 0.69 when compared with the manufacturer's rating of 0.7. There is however the need for the hot water supply system to be optimized as well as provision for supplementary heat source in order to maintain the appropriate operating temperature during low solar radiation levels. Copyright , Oxford University Press.

Date: 2012
References: Add references at CitEc
Citations:

Downloads: (external link)
http://hdl.handle.net/10.1093/ijlct/cts024 (application/pdf)
Access to full text is restricted to subscribers.

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:oup:ijlctc:v:7:y:2012:i:3:p:199-207

Access Statistics for this article

International Journal of Low-Carbon Technologies is currently edited by Saffa B. Riffat

More articles in International Journal of Low-Carbon Technologies from Oxford University Press
Bibliographic data for series maintained by Oxford University Press ().

 
Page updated 2025-03-19
Handle: RePEc:oup:ijlctc:v:7:y:2012:i:3:p:199-207