Performance comparison between R410A and R32 multi-heat pumps with a sub-cooler vapor injection in the heating and cooling modes
Il Yong Cho,
HyeongJoon Seo,
Dongwoo Kim and
Yongchan Kim
Energy, 2016, vol. 112, issue C, 179-187
Abstract:
The cooling and heating performances of R410A and R32 multi-heat pumps with a sub-cooler vapor injection (SCVI) were measured and compared with variations in the outdoor temperature, compressor speed, and injection ratio. Optimum injection ratios were determined to obtain maximum cooling and heating performances at a given operating condition. In the cooling mode with the optimum injection ratios, the R410A and R32 multi-heat pumps with vapor injection showed 2.1%–6.3% higher cooling capacity than those without vapor injection. In the heating mode, the R410A and R32 multi-heat pumps with vapor injection showed 7.5%–13.9% higher heating capacity than those without vapor injection, while showing 2.6%–7.0% and 1.1%–4.7% higher COPs, respectively. In addition, the SCVI cycle was more effective for improving the cooling and heating performances under extremely hot and cold weather conditions, respectively.
Keywords: Vapor injection; Multi-heat pump; Injection ratio; R410A; R32 (search for similar items in EconPapers)
Date: 2016
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (19)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S036054421630843X
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:energy:v:112:y:2016:i:c:p:179-187
DOI: 10.1016/j.energy.2016.06.069
Access Statistics for this article
Energy is currently edited by Henrik Lund and Mark J. Kaiser
More articles in Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().