Development and experimental validation of a transient 2D numeric model for radiant walls
Joaquim Romaní,
Luisa F. Cabeza and
Alvaro de Gracia
Renewable Energy, 2018, vol. 115, issue C, 859-870
Abstract:
An experimental set-up consisting of a house like cubicle exposed to outdoor weather was used to validate a numerical model of a radiant wall. The 2D transient finite volume model used as inputs the indoor temperature, outdoor temperature, global solar radiation incident on a vertical surface, and temperature and flow of the supply water. The simulation results closely agreed with the temperature profiles and heat fluxes for the three studied orientations (East, South, and West). Furthermore, a parametric study was carried out with the radiant wall model, concluding that pipes spacing between 125 mm and 150 mm and depth between 45 mm and 65 mm minimized the temperature difference on the surface while maximizing the heat flux. Furthermore, a control strategy with shorter activation periods improved the heat transfer efficiency.
Keywords: Thermally activated building systems (TABS); Radiant walls; Radiant heating; FVM; Numerical simulation (search for similar items in EconPapers)
Date: 2018
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (4)
Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0960148117307735
Full text for ScienceDirect subscribers only
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:eee:renene:v:115:y:2018:i:c:p:859-870
DOI: 10.1016/j.renene.2017.08.019
Access Statistics for this article
Renewable Energy is currently edited by Soteris A. Kalogirou and Paul Christodoulides
More articles in Renewable Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().