New Adaptive Reclosing Technique in Unbalanced Distribution System
Hun-Chul Seo
Additional contact information
Hun-Chul Seo: School of IT Engineering, Yonam Institute of Technology, Jinju 52821, Korea
Energies, 2017, vol. 10, issue 7, 1-16
Abstract:
The conventional reclosing of a distribution system is performed after a fixed dead time. However, it may lead to the increased outage time due to delayed reclosing. To solve this problem, this paper proposes a new adaptive reclosing scheme. The electrostatic induction is analyzed under at during-fault and post-fault conditions. Based on this analysis, the method to judge the fault clearance using the load current is proposed. The reclosing is adaptively performed after fault clearance. The distribution system and reclosing scheme are modelled by the electromagnetic transient program (EMTP). The various simulations according to the unbalanced ratio and various fault conditions are performed and analyzed. The superiority of the proposed scheme is verified by comparing with the conventional reclosing method.
Keywords: distribution system; electrostatic induction; EMTP; neutral current; reclosing (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2017
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (4)
Downloads: (external link)
https://www.mdpi.com/1996-1073/10/7/1004/pdf (application/pdf)
https://www.mdpi.com/1996-1073/10/7/1004/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:10:y:2017:i:7:p:1004-:d:104804
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().