Monitoring of MV Cable Screens, Cable Joints and Earthing Systems Using Cable Screen Current Measurements
Krzysztof Lowczowski,
Jozef Lorenc,
Andrzej Tomczewski,
Zbigniew Nadolny and
Jozef Zawodniak
Additional contact information
Krzysztof Lowczowski: Institute of Electric Power Engineering, Poznan University of Technology, Piotrowo 3A, 60965 Poznan, Poland
Jozef Lorenc: Institute of Electric Power Engineering, Poznan University of Technology, Piotrowo 3A, 60965 Poznan, Poland
Andrzej Tomczewski: Institute of Electrical Engineering and Electronics, Poznan University of Technology, Piotrowo 3A, 60965 Poznan, Poland
Zbigniew Nadolny: Institute of Electric Power Engineering, Poznan University of Technology, Piotrowo 3A, 60965 Poznan, Poland
Jozef Zawodniak: Department of Network Asset Management, Enea Operator, Strzeszynska 58, 60479 Poznan, Poland
Energies, 2020, vol. 13, issue 13, 1-28
Abstract:
The paper presents the possibility of using cable screen earthing current measurements for MV, single-core cable line monitoring. Cable screen earthing current measurement allows the condition of cable screen connections, degradation of earthing systems, and the earthing system integrity to be observed, which allows a condition based maintenance (CBM) strategy to be introduced for cable screens and earthing systems in MV networks. CBM allows the workload and failure rate to be reduced. Analysis of the condition of the cable screen and earthing system is carried out based on the cable screen earthing current trends and rapid changes of the current. The proposed system is integrated with a state of the art advanced metering infrastructure (AMI) and uses AMI data to calculate currents flowing through cable segments of the analyzed feeder. Additionally, a system which counts thermo-mechanical stresses associated with high current incidents in cable screens is proposed. The stresses are assessed using data from conventional protection relays and the ratio of currents in the cable core and cable screens. The stresses can be used as an indicator of the cable joint condition. The presented phenomena are studied carefully in PowerFactory software. Theoretical considerations are confirmed using measurements taken in the real MV cable line. Finally, the results of a SWOT analysis are presented and future research activities are outlined.
Keywords: earthing/grounding system; cable screen; quasi-dynamic simulation; advanced metering infrastructure (AMI); cable joint (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2020
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (4)
Downloads: (external link)
https://www.mdpi.com/1996-1073/13/13/3438/pdf (application/pdf)
https://www.mdpi.com/1996-1073/13/13/3438/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:13:y:2020:i:13:p:3438-:d:379904
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().