Using the Method of Harmonic Distortion Analysis in Partial Discharge Assessment in Mineral Oil in a Non-Uniform Electric Field
Alper Aydogan,
Fatih Atalar,
Aysel Ersoy Yilmaz and
Pawel Rozga
Additional contact information
Alper Aydogan: Department of Electrical and Electronic Engineering, Istanbul University-Cerrahpaşa, 34320 Avcilar, Istanbul, Turkey
Fatih Atalar: Department of Electrical and Electronic Engineering, Istanbul University-Cerrahpaşa, 34320 Avcilar, Istanbul, Turkey
Aysel Ersoy Yilmaz: Department of Electrical and Electronic Engineering, Istanbul University-Cerrahpaşa, 34320 Avcilar, Istanbul, Turkey
Pawel Rozga: Institute of Electrical Power Engineering, Lodz University of Technology, 90-924 Łódź, Poland
Energies, 2020, vol. 13, issue 18, 1-18
Abstract:
In high-voltage equipment, it is vital to detect any failure in advance. To do this, a determination of the partial discharges occurring at different voltage types as well as at different electrode configurations is essential for observing the oil condition. In this study, an experimental setup consisting of a needle–semi-sphere electrode configuration immersed in mineral oil is prepared for laboratory experiment. In such a way, a non-uniform electric field is created and the leakage currents are monitored from the grounded electrode. A total of six different electrode configurations are analyzed during the tests by the use of hemispheres of different diameters as grounded electrodes and copper and steel pointed (medical) needle high-voltage electrodes. In the experiments, the partial discharges occurring at four different voltage levels between 5.4 and 10.8 kV are measured and recorded. The effect of the different electrode configurations and voltage levels on the harmonic distortion are noted and discussed. It is experimentally confirmed that it is possible to measure the leakage current caused by the partial discharges of the corona type in oil at the different metal points, creating high-voltage electrodes and different electric field distributions based on the proposed non-invasive measurement technique. The studies showed that there is a significant rise of even harmonic components in the leakage current during the increase in the partial discharge intensity with the 5th harmonic as dominant.
Keywords: partial discharge; mineral oil; harmonic distortion; non-uniform electric field; discrete Fourier transform (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2020
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (3)
Downloads: (external link)
https://www.mdpi.com/1996-1073/13/18/4830/pdf (application/pdf)
https://www.mdpi.com/1996-1073/13/18/4830/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:13:y:2020:i:18:p:4830-:d:414061
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().