Combustible Material Content vs. Fire Properties of Electric Cables

Katarzyna Kaczorek-Chrobak and Jadwiga Fangrat
Additional contact information
Katarzyna Kaczorek-Chrobak: Instytut Techniki Budowlanej, Filtrowa 1, 00-611 Warszawa, Poland
Jadwiga Fangrat: Instytut Techniki Budowlanej, Filtrowa 1, 00-611 Warszawa, Poland

Energies, 2020, vol. 13, issue 23, 1-12

Abstract: The fire load of buildings is significantly increased by means of electric cables, usually creating a long combustible base for fire to spread and in this way decreasing the fire safety of buildings. The aim of the study was to evaluate a relationship between the construction of the cables and their fire properties, especially the mass loss influence on other fire properties of cables. Six cables of different core numbers were tested by means of the standard test method EN 50399. Additionally, thermogravimetric analysis and Attenuated Total Reflection—Fourier Transform Infrared analysis were performed on the separate outer sheath, bedding, and core insulations in order to determine the similarity of the materials’ chemical structures. It was found that: (1) the construction of the cable strongly influences the fire behavior due to the creation of a barrier for flame penetration and emission of combustion effluents though inside the closed agglomeration of non-combustible metallic cores (conductors), and the intumescent structures formed from aluminum trihydrate/zinc borate fillers and fire retardants in outer sheath material during the self-sustained combustion process after ignition of cables; (2) the inhomogeneous distribution of non-combustible inorganic fillers or different contents of fillers and flame retardants within the polymer fraction cause an unobvious fire behaviors of cables; and (3) the use of bedding in multicore cable construction results in lower values of combustion parameters (maximum average heat release rate, total heat release, maximum average smoke production rate, total smoke production), e.g., better fire properties of cables.

Keywords: construction of electric cables; reaction to fire of electric cables; fire safety of buildings (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2020
References: View references in EconPapers View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/1996-1073/13/23/6172/pdf (application/pdf)
https://www.mdpi.com/1996-1073/13/23/6172/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:13:y:2020:i:23:p:6172-:d:450363

Access Statistics for this article

Energies is currently edited by Ms. Agatha Cao

More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jeners:v:13:y:2020:i:23:p:6172-:d:450363