Analysis of a High-Voltage Room Quasi-Smoke Gas Explosion
Marit Sigfrid Bakka,
Erling Kristian Handal and
Torgrim Log
Additional contact information
Marit Sigfrid Bakka: Corporate Accident Investigations, Equinor, 5253 Sandsli, Norway
Erling Kristian Handal: Corporate Accident Investigations, Equinor, 5253 Sandsli, Norway
Torgrim Log: Department of Safety, Chemistry and Biomedical Laboratory Science, Fire Disaster Research Group, Western Norway University of Applied Sciences, 5528 Haugesund, Norway
Energies, 2020, vol. 13, issue 3, 1-14
Abstract:
During an air separation unit shut-down in a methanol production plant, a stop signal was sent to the control cabinet of a synchronous motor for a booster compressor. The control cabinet stopped magnetizing the rotor, while the system logic ensured that the power circuit breakers for the start reactor coils were opened, in order to be ready for the next start-up. Unintentionally, the circuit breaker was still connected (i.e., power was let through the reactors for a prolonged time period), which led to extensive overheating. Subsequently, the central control room received an unaddressed sub-station smoke alarm, and plant operators were sent out to locate the possible source of smoke. The accessible rooms were searched, and traces of smoke were confirmed. The Emergency Response Organization (ERO) was mustered and, through inspection, the Emergency Response Team (ERT) realized that the smoke originated from a ground floor high-voltage room. Fire hoses were arranged for fire extinguishing, and the ERT withdrew to wait for the room to be electrically isolated. About one minute after briefly opening the only set of doors to the high-voltage room, flames were observed, and a quasi-smoke gas explosion violently forced both door blades open and released a substantial fire ball. Personnel had been in the risk zone shortly before the explosion, but luckily no personnel were hit by the slamming door blades or the emerging flames. The incident revealed several learning points related to improper maintenance, ambiguous smoke alarm, lack of flame detectors in the high-voltage room, insufficient risk understanding and training regarding electrically related fire incidents, and the absence of an automatic fire suppression system. In plants processing hydrocarbons, the safety focus regarding hydrocarbon fire and explosion risk is paramount. However, risks related to electrical accidents and compartment fire dynamics (e.g., backdraft and smoke gas explosion) should also be given proper attention.
Keywords: quasi-smoke gas explosion; learning points; high-voltage room; electrical sub-station; safety measures (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2020
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (2)
Downloads: (external link)
https://www.mdpi.com/1996-1073/13/3/601/pdf (application/pdf)
https://www.mdpi.com/1996-1073/13/3/601/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:13:y:2020:i:3:p:601-:d:314291
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().