EconPapers    
Economics at your fingertips  
 

Performance Analysis of Real-Scale 23 kV/60 MVA Class Tri-Axial HTS Power Cable for Real-Grid Application in Korea

Seok-Ju Lee, Seong Yeol Kang, Minwon Park, DuYean Won, Jaeun Yoo and Hyung Suk Yang
Additional contact information
Seok-Ju Lee: Mechatronics Research Institute, Changwon National University, Changwon 641-773, Korea
Seong Yeol Kang: Department of Electrical Engineering, Changwon National University, Changwon 641-773, Korea
Minwon Park: Department of Electrical Engineering, Changwon National University, Changwon 641-773, Korea
DuYean Won: KEPCO Research Institute, Daejeon 34056, Korea
Jaeun Yoo: KEPCO Research Institute, Daejeon 34056, Korea
Hyung Suk Yang: KEPCO Research Institute, Daejeon 34056, Korea

Energies, 2020, vol. 13, issue 8, 1-13

Abstract: Currently, various types of superconducting power cables are being developed worldwide, and research and development of a tri-axial high-temperature superconducting (HTS) power cable are underway. The tri-axial HTS power cable reduces the amount of HTS wire due to its multilayer structure, has high current characteristics, and has less loss than other superconducting cables. However, since the radii of each phase are different, magnetic coupling makes it difficult to measure power loss and analyze performance. This paper presents the results of the design and performance analysis of a tri-axial HTS power cable. A prototype tri-axial HTS power cable was designed with a rated power of 60 MVA, a rated voltage of 23 kV and a length of 6 m, and was tested by cooling to 77 K with liquid nitrogen. We analyzed the performance of the tri-axial HTS power cable in normal conditions through a finite element method (FEM) simulation and experiment. The alternating current (AC) loss of the tri-axial HTS power cable was calculated using a FEM program based on the Maxwell equation, and the result was used to confirm the AC loss of the tri-axial HTS power cable prototype measured by the electrical measurement method. In conclusion, in the current test of a tri-axial HTS cable designed as 23 kV/60 MVA, the DC critical current was over 6000 A, the AC loss was approximately 0.24 W/m, and the simulation and analysis design values were satisfied. The results of this study will be effectively applied to commercial tri-axial HTS power cable development to be installed in a real power system. This means that the actual tri-axial HTS cable has sufficient capacity for rated current operation in the system where it will be applied, and the actual measurement of the cable loss can be applied as an important factor in the design of the cooling capacity of the entire superconducting cable, which consists of several kilometers.

Keywords: high temperature superconducting (HTS) cable; tri-axial HTS cable; AC loss (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2020
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (4)

Downloads: (external link)
https://www.mdpi.com/1996-1073/13/8/2053/pdf (application/pdf)
https://www.mdpi.com/1996-1073/13/8/2053/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:13:y:2020:i:8:p:2053-:d:348107