Fuse-Fuse Protection Scheme ETAP Model for IEEE 13 Node Radial Test Distribution Feeder
Kemei Peter Kirui,
David K. Murage and
Peter K. Kihato
Additional contact information
Kemei Peter Kirui: Department of Electrical and Electronic Engineering, JKUAT, Kenya
David K. Murage: Department of Electrical and Electronic Engineering, JKUAT, Kenya
Peter K. Kihato: Department of Electrical and Electronic Engineering, JKUAT, Kenya
European Journal of Engineering and Technology Research, 2019, vol. 4, issue 9, 224-234
Abstract:
According to NEC 240.101 regulations each and every component of a power system distribution network has to have an over-current protective device (OCPD) for its protection. The OCPDs must coordinate with other devices both upstream and downstream for a reliable operation and protection of the power systems distribution network. There are four equipment/components for the IEEE 13 node radial test feeder each modelled in this paper to be protected by fuses. These components are namely the nodes, the underground cables, the overhead distribution lines and the transformers. Equipment protection is an important and necessary exercise of performing power systems protection coordination processes. The equipment and their over-current protective device’s time-current characteristic (TCC) curves are important tools used to show and to indicate the protection requirements, landmark points and damage curves for all power systems equipment. Individual equipment protection requirements and limitations are described and identified by use of their various landmarks and damage curves. These damage curves and the landmark points are all superimposed with the Time-Current Characteristic curves of the Over-Current Protective Devices used in protecting the equipment on one composite TCC graph. Equipment damage curves which fall to the right and above the Over-Current Protective Device’s TCC curves with sufficient margins are considered to be protected by the OCPDs. Equipment damage curves which fall to the left and below the OCPD’s TCC curves are considered not to be protected by the OCPDs. IEEE Standard 241 states that on all power systems, the OCPDs should be selected and set to open before the Ampacity mark, the short circuit damage curves, and both the thermal and the mechanical damage curves limits of the protected components are exceeded. This paper presents a detailed Fuse-Fuse protection scheme for the IEEE 13 node radial test feeder as modeled on the Electrical Transients Analysis Program (ETAP).
Keywords: Transformer Magnetizing In-rush Points; Transformer Thermal Damage Curves; Transformer Mechanical Damage Curves; Transformer Full Load Ampere Mark; Conductor Intermediate Thermal Overload Limit Curves; Conductor Short Circuit Damage Curves; Fuse TCC Curves; Equipment TCC Curves (search for similar items in EconPapers)
Date: 2019
References: Add references at CitEc
Citations:
Downloads: (external link)
https://eu-opensci.org/index.php/ejeng/article/view/61549 Abstract page (text/html)
https://eu-opensci.org/index.php/ejeng/article/download/61549/12196 Full text (application/pdf)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:epw:ejeng0:v:4:y:2019:i:9:id:61549
DOI: 10.24018/ejeng.2019.4.9.1549
Access Statistics for this article
More articles in European Journal of Engineering and Technology Research from European Open Science
Bibliographic data for series maintained by Support ().