Proposal and Validation of a Pyro Conductor Switch-Based FCL for DC Distribution System Protection
Il Kwon,
Yu-Jin Kwak,
Jeong-Cheol Lee and
Bang-Wook Lee ()
Additional contact information
Il Kwon: Department of Electronic Engineering, Hanyang University, Ansan 15588, Republic of Korea
Yu-Jin Kwak: Department of Electronic Engineering, Hanyang University, Ansan 15588, Republic of Korea
Jeong-Cheol Lee: Department of Electronic Engineering, Hanyang University, Ansan 15588, Republic of Korea
Bang-Wook Lee: Department of Electronic Engineering, Hanyang University, Ansan 15588, Republic of Korea
Energies, 2025, vol. 18, issue 13, 1-15
Abstract:
With the increasing deployment of DC power systems, particularly in DC distribution systems, there is a growing demand for rapid and effective fault current limiting solutions. Conventional fault current limiters (FCLs) often suffer from limitations in terms of response time, size, and operational complexity. As a solution to these challenges, this paper proposes a hybrid FCL based on a pyro conductor switch (PCS), which combines passive limiting elements with an active switching mechanism. The proposed PCS FCL consists of a pyro fuse, an IGBT switch, a limiting inductor, and a damping resistor. Upon fault detection, the IGBT switch is first turned off to initiate current transfer into the limiting branch. Subsequently, the pyro fuse operates by explosively severing the embedded conductor using a pyrotechnic charge, thereby providing galvanic isolation and reinforcing current commutation into a high-impedance path. This operational characteristic enables effective fault current suppression without requiring complex control or real-time sensing. A detailed analysis using PSCAD/EMTDC simulations was conducted to evaluate the current limiting characteristics under fault conditions, and a prototype was subsequently developed to validate its performance. The simulation results were verified through experimental testing, indicating the limiter’s ability to reduce peak fault current. Furthermore, the results demonstrated that the degree of current limitation can be effectively designed through the selection of appropriate current limiting parameters. This demonstrates that the proposed PCS-based FCL provides a practical and scalable solution for improving protection in DC power distribution systems.
Keywords: DC distribution system; fault current limiter; FCL prototype; PCS (pyro conductor switch) (search for similar items in EconPapers)
JEL-codes: Q Q0 Q4 Q40 Q41 Q42 Q43 Q47 Q48 Q49 (search for similar items in EconPapers)
Date: 2025
References: Add references at CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/1996-1073/18/13/3441/pdf (application/pdf)
https://www.mdpi.com/1996-1073/18/13/3441/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jeners:v:18:y:2025:i:13:p:3441-:d:1691421
Access Statistics for this article
Energies is currently edited by Ms. Agatha Cao
More articles in Energies from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().