Shengpeng Chen, Peng Xu, Juan Shi, Lisha Sheng, Chaoling Han () and Zhenqian Chen ()
Additional contact information
Shengpeng Chen: College of Emergency Management, Nanjing Tech University, Nanjing 211816, China
Peng Xu: School of Energy and Environment, Southeast University, Nanjing 210096, China
Juan Shi: School of Energy and Environment, Southeast University, Nanjing 210096, China
Lisha Sheng: School of Energy and Environment, Southeast University, Nanjing 210096, China
Chaoling Han: College of Emergency Management, Nanjing Tech University, Nanjing 211816, China
Zhenqian Chen: School of Energy and Environment, Southeast University, Nanjing 210096, China

Sustainability, 2023, vol. 15, issue 24, 1-20

Abstract: The current situation of high energy consumption in data centers places high demands on the energy consumption and heat-dissipation efficiency of cooling technology. This article studies the steady-state flow and heat-transfer characteristics of a pump-driven separated heat pipe system from an experimental perspective. After designing and selecting the pump-driven microchannel-separated heat pipe system, an experimental platform is built to test the pump-driven microchannel-separated heat pipe system under variable operating conditions. It is found that the optimal filling rate range of the system is 75% to 95%, and the optimal condensing air volume is 4250 m 3 /h. The relationship between the circulating mass flow rate and the heat-transfer capacity of the heat pipe system is comprehensively influenced by the resistance of each section and the heat-transfer coefficient at the heat exchanger. When the indoor and outdoor temperature difference increases from 10 °C to 30 °C, the heat transfer increases by 261.5%, and the working medium of R410a has a better heat-transfer performance than R134A at outdoor temperatures ranging from 0 to 15 °C. The results contribute to the application of pump-assisted microchannel heat pipe systems in data center machines, which provide guidance for the application of cabinet-level thermal management.

Keywords: pump drive; separated heat pipe; filling rate; microchannel; working medium (search for similar items in EconPapers)
JEL-codes: O13 Q Q0 Q2 Q3 Q5 Q56 (search for similar items in EconPapers)
Date: 2023
References: View references in EconPapers View complete reference list from CitEc
Citations:

Downloads: (external link)
https://www.mdpi.com/2071-1050/15/24/16839/pdf (application/pdf)
https://www.mdpi.com/2071-1050/15/24/16839/ (text/html)

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:gam:jsusta:v:15:y:2023:i:24:p:16839-:d:1300152

Access Statistics for this article

Sustainability is currently edited by Ms. Alexandra Wu

More articles in Sustainability from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().

 
Page updated 2025-03-19
Handle: RePEc:gam:jsusta:v:15:y:2023:i:24:p:16839-:d:1300152