Abstract:
Determination of airflow rates is an inevitable part of the energy-efficient control of ventilation systems. To achieve efficient control, the flowmeters used must be suitably accurate and create minimum disturbance to the airflow. In this study, we evaluate the quantitative performance characteristics of an innovative micro-electromechanical systems (MEMS) flowmeter, a so-called Elastic Filament Velocimetry (EFV), in ventilation ducts. Two versions of the EFV-sensor, i.e., an 11-nanoribbon and a 22-nanoribbon variety, were evaluated in laboratory studies. The results indicate that the 11-nanoribbon sensor is more suitable for air velocity measurements in ducts than the 22-nanoribbon sensor. The 11-nanoribbon sensor can measure air velocities from 0.3 m/s. The maximum variation of the sensor-output is 3% for velocities over 0.5 m/s. Calibration models have been developed for the 11-nanoribbon sensor. The error due to model calibration is lower than ±5% for velocities over 0.6 m/s. Moreover, laboratory studies were performed to investigate the airflow disturbance in a duct system due to the EFV sensor. The results were compared with the corresponding disturbance caused by two different types of self-averaging probes. At a bulk velocity of 3 m/s, the self-averaging probes introduced a greater pressure drop by at least 50% compared to the EFV-sensor.
Keywords: EFV-sensor; MEMS airflow sensor; air velocity measurements; flow disturbance; ventilation systems (search for similar items in EconPapers)
JEL-codes: O13 Q Q0 Q2 Q3 Q5 Q56 (search for similar items in EconPapers)
Date: 2023
References: View complete reference list from CitEc
Citations:
Downloads: (external link)
https://www.mdpi.com/2071-1050/15/3/1955/pdf (application/pdf)
https://www.mdpi.com/2071-1050/15/3/1955/ (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:gam:jsusta:v:15:y:2023:i:3:p:1955-:d:1041673
Access Statistics for this article
Sustainability is currently edited by Ms. Alexandra Wu
More articles in Sustainability from MDPI
Bibliographic data for series maintained by MDPI Indexing Manager ().