A Method for Identification of Transformer Inrush Current Based on Box Dimension
Maofa Gong,
Ran Zheng,
Linyuan Hou,
Jingyu Wei and
Na Wu
Mathematical Problems in Engineering, 2017, vol. 2017, 1-6
Abstract:
Magnetizing inrush current can lead to the maloperation of transformer differential protection. To overcome such an issue, a method is proposed to distinguish inrush current from inner fault current based on box dimension. According to the fundamental difference in waveform between the two, the algorithm can extract the three-phase current and calculate its box dimensions. If the box dimension value is smaller than the setting value, it is the inrush current; otherwise, it is inner fault current. Using PSACD and MATLAB, the simulation has been performed to prove the efficiency reliability of the presented algorithm in distinguishing inrush current and fault current.
Date: 2017
References: Add references at CitEc
Citations:
Downloads: (external link)
http://downloads.hindawi.com/journals/MPE/2017/2095896.pdf (application/pdf)
http://downloads.hindawi.com/journals/MPE/2017/2095896.xml (text/xml)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:hin:jnlmpe:2095896
DOI: 10.1155/2017/2095896
Access Statistics for this article
More articles in Mathematical Problems in Engineering from Hindawi
Bibliographic data for series maintained by Mohamed Abdelhakeem ().