Performance Study of a Four-Bed Silica Gel-Water Adsorption Chiller with the Passive Heat Recovery Scheme
Zhilong He,
Xiaolin Wang and
Hui Tong Chua
Mathematical Problems in Engineering, 2015, vol. 2015, 1-10
Abstract:
Adsorption chiller technology is one of the effective means to convert waste thermal energy into effective cooling, which substantially improves energy efficiency and lowers environmental pollution. This paper uses an improved lump-parameter design model to theoretically and experimentally evaluate the efficacy of the passive heat recovery scheme as applied to a four-bed adsorption chiller. Results show that the model can accurately track the experimental temporal system outlet temperatures. The performance predictions from this model compare favourably with experimental results. At rated temperature conditions and over a wide range of cycle times, both the cooling capacity and COP can be predicted to within 12.5%. The analyses indicate that the model can be used confidently as a design tool for a four-bed adsorption chiller and the passive heat recovery scheme can effectively improve the system performance.
Date: 2015
References: Add references at CitEc
Citations:
Downloads: (external link)
http://downloads.hindawi.com/journals/MPE/2015/634347.pdf (application/pdf)
http://downloads.hindawi.com/journals/MPE/2015/634347.xml (text/xml)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:hin:jnlmpe:634347
DOI: 10.1155/2015/634347
Access Statistics for this article
More articles in Mathematical Problems in Engineering from Hindawi
Bibliographic data for series maintained by Mohamed Abdelhakeem ().