FEM Application for Evaluating and Improving the Insulation System of the 33kV Wound-Core Type Distribution Transformer
Kassim R. Hameed and
Ibraheem J. Jabur
Modern Applied Science, 2018, vol. 12, issue 9, 39
Abstract:
This paper presents a 2-D & 3-D FE model of 250kVA, 33/0.416 kV wound core type distribution transformer, simulated using ANSYS 17.2 software in order to evaluate the insulation system via dielectric strength under power frequency and induced withstand tests and using two types of analysis, time-harmonic analysis to simulate the dielectric tests, and electro-static analysis to calculate the capacitance matrix. The assessment is based on the maximum allowable electric field intensity. the obtained results were compared with those of the real test, and the values of electric stress were less than the maximum allowable values. also, improvements to the presented model were applied following the transformer assessment. The improvement to the transformer insulation structure was done using three suggested finite element models included reduction and changing the materials type. the results were reviewed in form of contour plots, vector plots, and curves.
Date: 2018
References: View complete reference list from CitEc
Citations:
Downloads: (external link)
https://ccsenet.org/journal/index.php/mas/article/download/76390/42654 (application/pdf)
https://ccsenet.org/journal/index.php/mas/article/view/76390 (text/html)
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:ibn:masjnl:v:12:y:2018:i:9:p:39
Access Statistics for this article
More articles in Modern Applied Science from Canadian Center of Science and Education Contact information at EDIRC.
Bibliographic data for series maintained by Canadian Center of Science and Education ().