Inverse Problem of Voltage over Electrostatic Shield Gap in Helical Transformer Windings
Petar Bodlovic (),
Kemal Hot and
Tomislav Kelemen
Additional contact information
Petar Bodlovic: Polytechnic of Zagreb, Electrical Engineering Department
Kemal Hot: Polytechnic of Zagreb, Electrical Engineering Department
Tomislav Kelemen: Polytechnic of Zagreb, Electrical Engineering Department
A chapter in Optimization and Inverse Problems in Electromagnetism, 2003, pp 233-244 from Springer
Abstract:
Abstract Multi-conductor transmission line model of a helical winding for an analysis of the very fast electromagnetic transients will include the lumped voltage between the edges of the open electrostatic screen, previously found to be responsible for experimentally found anomalous distortion of the travelling waves. Contrary to the former model with distributed voltage and axial symmetry, the new model requires parameters beyond those of classical theories of wave propagation in transformer windings. The additional parameters are found by matching the simulated voltage transients with the experimental results.
Keywords: Multiconductor transmission-line theory; anomalous distortion; travelling waves; inverse problem (search for similar items in EconPapers)
Date: 2003
References: Add references at CitEc
Citations:
There are no downloads for this item, see the EconPapers FAQ for hints about obtaining it.
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:spr:sprchp:978-94-017-2494-4_23
Ordering information: This item can be ordered from
http://www.springer.com/9789401724944
DOI: 10.1007/978-94-017-2494-4_23
Access Statistics for this chapter
More chapters in Springer Books from Springer
Bibliographic data for series maintained by Sonal Shukla () and Springer Nature Abstracting and Indexing ().