Pontiac fever outbreak associated with a cooling tower
S. Friedman,
K. Spitalny,
J. Barbaree,
Y. Faur and
R. McKinney
American Journal of Public Health, 1987, vol. 77, issue 5, 568-572
Abstract:
In late April 1984, an outbreak of Pontiac fever was investigated in an office building in lower Manhattan (New York City). The outbreak was characterized by a high attack rate (78 per cent overall); the predominant symptoms were myalgias, chills, fatigue, fever, and headache. There was a clustering of cases in an office that was air cooled by a dedicated cooling tower separate from the remainder of the building. A high concentration of live L. Pneumophilia cells in the cooling tower was quantified. Airborne spread via settle plates placed along the air intake system and within the office was demonstrated. Legionella pneumophilia serogroup 1 antigen was found in the urine of two cases, and identical monoclonal antibody reactivity patterns of isolates from all sources was observed. Difficulty was experienced in eliminating the organism from the tower.
Date: 1987
References: Add references at CitEc
Citations: View citations in EconPapers (1)
There are no downloads for this item, see the EconPapers FAQ for hints about obtaining it.
Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.
Export reference: BibTeX
RIS (EndNote, ProCite, RefMan)
HTML/Text
Persistent link: https://EconPapers.repec.org/RePEc:aph:ajpbhl:1987:77:5:568-572_1
Access Statistics for this article
American Journal of Public Health is currently edited by Alfredo Morabia
More articles in American Journal of Public Health from American Public Health Association
Bibliographic data for series maintained by Christopher F Baum ().