A model to compare convective and radiant heating systems for intermittent space heating

Zhe Wang, Maohui Luo, Yang Geng, Borong Lin and Yingxin Zhu

Applied Energy, 2018, vol. 215, issue C, 226 pages

Abstract: In this paper, a dynamic heat transfer model based on thermal-electrical analogy has been built to compare convective and radiative heating systems for intermittent heating. An experiment has been set up to validate the model we built. The RMS Error was within 0.5 °C, confirming the accuracy of the model. The validated model was then applied to compare four typical space heating systems, namely all-air, radiator, in-slab floor heating, and lightweight floor heating systems. The concept of “ineffective heat” has been proposed to explain why the intermittent heating could reduce heating load. Two ideal characters of heating systems have been identified for intermittent heating, i.e. high heating capacity and low thermal mass, both of which are crucial to shorten the preheat time and to reduce the ineffective heat. The results indicate that convective heating systems were more comfortable (more rapidly raise the indoor temperature) and more energy efficient (lower heating load) for intermittent operation than radiative heating systems. The performance gap between radiative and convective heating systems would be enlarged in colder conditions. Among the four heating systems, convective heating system was the most suitable one for intermittent heating, and floor heating was the most unsuitable one. Though belonging to radiative heating systems, the radiator performs differently from floor heating for its potential to enhance heating capacity and relatively low thermal mass. Additionally, outdoor climate and building thermal insulation level also affect the choice of the most suitable heating system and heating mode. The findings of this research might shed some light on the debate of the choice of space heating systems in areas with similar climate conditions with China’s Hot Summer Cold Winter region.

Keywords: Convective heating systems; Radiant heating systems; Intermittent space heating; Thermal-electrical analogy; China’s Hot Summer Cold Winter Region (search for similar items in EconPapers)
Date: 2018
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (9)

Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S030626191830103X
Full text for ScienceDirect subscribers only

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:eee:appene:v:215:y:2018:i:c:p:211-226

Ordering information: This journal article can be ordered from
http://www.elsevier.com/wps/find/journaldescription.cws_home/405891/bibliographic
http://www.elsevier. ... 405891/bibliographic

DOI: 10.1016/j.apenergy.2018.01.088

Access Statistics for this article

Applied Energy is currently edited by J. Yan

More articles in Applied Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().

 
Page updated 2025-03-19
Handle: RePEc:eee:appene:v:215:y:2018:i:c:p:211-226