EconPapers    
Economics at your fingertips  
 

Performance investigation of an internally cooled desiccant wheel

Xingchao Zhou, Mark Goldsworthy and Alistair Sproul

Applied Energy, 2018, vol. 224, issue C, 382-397

Abstract: Desiccant wheels are commonly used to dehumidify air in air-conditioning system to reduce the energy consumption. The objective of this study was to design, test and analyse the performance of a novel tube-shell, internally water-cooled desiccant wheel. Cooling water was used in the supply section of the new wheel to shift the dehumidification process from nearly adiabatic to nearly isothermal. We conducted a series of experiments to investigate the wheel’s performance and used the experimental results to validate a mathematical model. The model was then applied to investigate the influence of modifications to the base design, including changing the number of desiccant layers inside the heat-exchange tubes, and the size and number of tubes. We also analysed the influence of water temperature and flow rate on both dehumidification and temperature rise across the wheel. Our results show that isothermal dehumidification performance can be achieved, but only with no more than two desiccant layers inside the heat-exchange tubes. More layers reduced heat transfer between the air in the innermost layers and the cooling water. Lower cooling water inlet temperatures led to lower air outlet humidity and temperature. A cooling water temperature of approximately 24 °C was required to achieve isothermal dehumidification for process air with inlet temperature of 30 °C and absolute humidity of 16.3 g/kg and regeneration air with the inlet temperature of 50 °C and absolute humidity of 16.3 g/kg. This corresponds to a 48% improvement in dehumidification performance (the maximum absolute humidity change between inlet and outlet process air) compared with a conventional adiabatic desiccant wheel while using super-adsorbent polymer as the desiccant material.

Keywords: Desiccant wheel; Non-adiabatic process; Dehumidification; Air conditioning (search for similar items in EconPapers)
Date: 2018
References: View references in EconPapers View complete reference list from CitEc
Citations: View citations in EconPapers (8)

Downloads: (external link)
http://www.sciencedirect.com/science/article/pii/S0306261918307049
Full text for ScienceDirect subscribers only

Related works:
This item may be available elsewhere in EconPapers: Search for items with the same title.

Export reference: BibTeX RIS (EndNote, ProCite, RefMan) HTML/Text

Persistent link: https://EconPapers.repec.org/RePEc:eee:appene:v:224:y:2018:i:c:p:382-397

Ordering information: This journal article can be ordered from
http://www.elsevier.com/wps/find/journaldescription.cws_home/405891/bibliographic
http://www.elsevier. ... 405891/bibliographic

DOI: 10.1016/j.apenergy.2018.05.011

Access Statistics for this article

Applied Energy is currently edited by J. Yan

More articles in Applied Energy from Elsevier
Bibliographic data for series maintained by Catherine Liu ().

 
Page updated 2025-03-19
Handle: RePEc:eee:appene:v:224:y:2018:i:c:p:382-397